2008-03-27 11:28:14RESIDENTIAL ADDITION, BUILDING REVIEW 4TH CHECKLIST.
 REVIEW UNDER FBC 2004 WITH 2007 REVISIONS.
 1- ENERGY CALCULATIONS NEED TO BE SIGNED AND DATED BY
 THE OWNER/AGENT.
  
 2- REVISIONS ON SURVEY NEED TO BE DONE BY THE SURVEYOR.
 (REPEAT COMMENT).SURVEYOR TO REVISE FLOOD ZONE "C" TO
 "B" AND PROVIDE REVISED SURVEY WITH ORIGINAL SEAL AND
 SIGNATURE AS REQUIRED BY CHAPTER 472 FLORIDA STATUTE
 AND SEC. 61G17-7.0025 FLORIDA ADMINISTRATIVE CODE.
 NOTE: MAKE SURE ORIGINAL SIGNATURE IS PROVIDED. RUBBER
 STAMP OR PHOTOCOPY OF SIGNATURE IS NOT ALLOWED.
  
 3- STORM SHUTTERS:
 A) THERE WAS NOT PRODUCT APPROVAL SUBMITTED.
  
 B) INSTALLATION SCHEDULE SUBMITTED NEED TO BE
 CORRECTED:
 I) THERE ARE TWO DIFFERENT TYPES OF ANCHORS SPECIFIED:
 TAPCON AND TITEN. SEESHUTTER PRODUCT APPROVAL AND
 SPECIFIED AND MARK SPECIFIC ANCHOR TO BE USED.
  
 II) OPENINGS 6 AND 7 ARE THE SAME SIZE WINDOWS. HOW
 COME OPENING SIZES ARE DIFFERENT. REVISE AS REQUIRED.
  
 III) SHUTTER MOUNTING CONDITIONS ON COLUMN 4 IS ASKING
 FOR MOUNTING CONDITION. EG: WALL MOUNTED, BUILT OUT,
 ETC. NOT FOR ANCHOR TYPE.SEE SHUTTERS PRODUCT
 APPROVAL AND WRITE DOWN ON THIS COLUMN AND MARK
 SHUTTERS DRAWINGS WITH THAT MOUNTING CONDITION.
  
 IV) CLARIFY HOW ARE YOU GETTING THE 4" GLASS SEPARATION
 SHOWN ON COLUMN 5.
  
 V) SHUTTER SPANS SPECIFIED ON COLUMN 6 ARE WRONG.THEY
 ARE SHOWN AS THE SAME HEIGHT AS THE OPENING.THIS
 DOESN'T ALLOW THE 3" EDGE DISTANCE SPECIFIED ON COLUMN
 8. REVISE AS REQUIRED.
  
 VI) MINIMUM EDGE DISTANCE SPECIFIED ON COLUMN #8 IS 3"
 EDGE DISTANCE.SEE STORM SHUTTERS DRAWINGS FOR
 REQUIRED ANCHOR SPACING REDUCTION WHEN EDGE DISTANCE IS
 LESS THAN 3.5" AND REVISE ANCHOR SPACING ACCORDINGLY.
  
 VII) CLARIFY HOW ARE THE ANCHORS GOING TO BE SPACED AT
 6.5" . SEESHUTTERS DRAWINGS FORWIDTH OF STORM
 PANELS AND LOCATION OF ANCHORS. AND REVISE AS
 REQUIRED.
  
 VIII) CLEARLY MARK ON STORM SHUTTER DRAWINGS SPECIFIC
 MOUNTING CONDITIONS (EG: WALL MOUNTED, BUILT OUT, ETC)
 AND SPECIFIC ANCHOR TO BE USED ACCORDING TO THE DESIGN
 PRESSURES, CONNECTION TYPE, PANEL SPAN, EDGE DISTANCE
 AND STRUCTURE TO BE ATTACHED TO (MASONRY OR CONCRETE
 BLOCK).
  
 4- NONE OF THE PRODUCT APPROVALS REQUIRED BY DCA RULE
 9B-72 WHERE SUBMITTED THIS TIME. NEED TO PROVIDE
 PRODUCT APPROVALS FOR: DOORS, WINDOWS, ROOF SHINGLES,
 SHUTTERS, SIMPSON STRUCTURAL CONNECTORS.
  
 5- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
  
 6- SHEET 1:REVISE CONSTRUCTION STANDARD. THERE IS NOT
 "5 STD CBS". SEE SEC. 602.5 AND TABLE 601 OF FLORIDA
 BUILDING CODE 2004 AND SPECIFY IF CONSTRUCTION TYPE IS
 TYPE VA OR B.
  
 7- DRAWINGS SUBMITTED NOW DON'T HAVE THE PALM BEACH
 COUNTY IMPACT FEES STAMP. PLEASE PROVIDE OLD PAGEWITH
 THE IMPACT FEES STAMP OR GET THE REVISED SHEETS
 RE-STAMPED.
  
 8- SOIL TEST REPORT:
 A) SOIL TEST REPORT CALLS FOR 2000 PSF SOIL BEARING
 CAPACITY.ENGINEER OF RECORD SPECIFIES ON STRUCTURAL
 NOTE #1 THAT 200 PSF SOIL BEARING CAPACITY IS REQUIRED.
 ENGINEER OF RECORD TO COORDINATE WITH GEOTECHNICAL
 ENGINEER FOR SOIL BEARING CAPACITY REQUIRED AND ACTUAL
 SOIL BEARING CAPACITY TO BE PROVIDED. REVISE AS
 REQUIRED.
  
 B) ONLY ONE REPORT WAS SUBMITTED.NEED TO PROVIDE
 2 REPORTSWITH ORIGINAL SEAL AND SIGNATURE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712