2007-11-27 08:59:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 05 & 06 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS
 TO CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON THE
 PREVIOUS REVIEWS, 9/6/07 OR 10/17/07:
  
 1. SHEET 2, SANITARY RISER DIAGRAM: THE WASHING
 MACHINE AND SINK IN THE UTILITY ROOM MUST DRAIN
 DOWNSTREAM OF THE WET VENTEDBATHROOM GROUP. PER FBC,
 PLUMBING, SECTION *909.1 WET VENT PERMITTED.
  
 2. SHEET 2, SANITARY RISER DIAGRAM A CLEANOUT IS
 REQUIRED AT THE BASE OF THE WASTE STACK IN THE PROPOSED
 BATHROOM. PER FBC, PLUMBING, SECTION *708.3.4 BASE OF
 STACK.
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED ON THE
 PREVIOUS REVIEW, 10/17/07:
  
 3. SHEET 2, SANITARY RISER DIAGRAM: THE WASHING
 MACHINE IS "S" TRAPPED AND A VENT IS REQUIRED. PER FBC,
 PLUMBING, SECTIONS *1002.3 PROHIBITED TRAPS AND
 *901.2.1 VENTING REQUIRED.
  
 4. THE RESUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE
 FOR THE ADDITION DUE TO THE FACT THAT THE WATER HEATER
 IS IN THE NEW ADDITION UTILITY ROOM AND THE ENERGY
 CALCULATIONS ARE INDICATING PER (14) HOT WATERSYSTEM
 TYPE, N/A. PER THE FOLLOWING CHAPTER 13 ENERGY
 EFFICIENCY SECTION 13-101.0 GENERAL. THIS CODE IS A
 STATEWIDE UNIFORM CODE AND SHALL NOT BE MADE MORE
 STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE CODE
 PROVIDES FOR A UNIFORM STANDARD OF ENERGY EFFICIENCY
 BY, AT A MINIMUM, SETTING FORTH MINIMUM REQUIREMENTS
 FOR EXTERIOR ENVELOPES, LIGHTING, ELECTRICAL
 DISTRIBUTION, AND SELECTION OF HEATING, LIGHTING,
 VENTILATION, AIR CONDITIONING AND SERVICE WATER HEATING
 SYSTEMS. IT SHALL APPLY TO ALL NEW BUILDINGS, TO
 ADDITIONS TO EXISTING BUILDINGS AND MANUFACTURED HOMES,
 TO RENOVATIONS TO EXISTING BUILDINGS, BOTH PUBLIC AND
 PRIVATE, WITH CERTAIN EXCEPTIONS, TO CHANGES OF
 OCCUPANCY TYPE, TO THE SITE-INSTALLED COMPONENTS AND
 FEATURES OF A MANUFACTURED HOMES AT THEIR FIRST SET-UP,
 AND TO THE INSTALLATION OR REPLACEMENT OF BUILDING
 SYSTEMS AND COMPONENTS WITH NEW PRODUCTS FOR WHICH
 THERMAL EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW
 BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND
 IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF
 INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH
 SUBCHAPTER 13-4 OR 13-6 OF THIS CODE.
 **NOTE: THE WATER HEATER IN THE NEW ADDITION UTILITY
 ROOM SHALL COMPLY PER THE FOLLOWING AND BE INDICATED ON
 THE RESUBMITTED ENERGY CALCULATIONS:
  
 A} 13-101.2.2 ADDITIONS.
 B} TABLE 13-612.1.ABC.3.2, MINIMUM PERFORMANCE
 STANDARDS, WATER HEATING EQUIPMENT.
  
 THE FOLLOWING IS A NEW COMMENT:
  
 5. SEE ATTACHED IMPORTANT NOTICE FS 553.80(2)(B)
 DESIGN PROFESSIONAL DOCUMENTS REGUARDING FOUR (4) TIMES
 THE FEE.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  