Plan Review Notes
Plan Review Notes For Permit 07080417
Permit Number 07080417
Review Stop E
Sequence Number 3
Notes
Date Text
2007-11-19 12:25:06 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
 THE FOLLOWING COMMENTS ARE REGARDING THE ELECTRICAL
 DRAWINGS ON SHEET 2 OF 2.
  
 THESE COMMENTS WERE NOT ADDRESSED ON THE PREVIOUS
 REVIEW, 8/27/07, OR ON THE 11/19/07 REVIEW.
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, PROVIDE AN AIC RATING, ANDLOCATE
 ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER
 DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE.* THE
 AIC RATING IS NOT ON THE PLAN.** SAME COMMENT
 11/19/07.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. THERE IS NO CONDENSER # 2 ON THE SCHEDULE
 PROVIDED AND APPLIANCES THAT ARE IN THE CALCULATION ARE
 MISSING. SEE 408.4 2005 NEC. *THERE ARE STILL
 APPLIANCES MISSING FROM THE SCHEDULE. SMALL APPLIANCE,
 WASHER AND THE TERMS "CONV. OUTLETS AND GEN LIGHTING"
 ARE NOT SPECIFIC ENOUGH TO MEET THE INTENT OF
 408.4.**SAME COMMENT 11/19/07.
  
 3} THERE IS 10000 VA OF HEAT IN THE LOAD CALCULATION,
 CORRECTLY CALCULATED AT 100% PER 220.83(B), BUT THE
 PANEL SCHEDILE INDICATES 2 AIR HANDLERS WITH AN OCP OF
 60 AMPS, WHICH WOULD IMPLY THAT THERE ARE 2 UNITS WITH
 10000 VA EACH. PLEASE CLARIFY. *IF THE AHU'S ARE 5KW
 EACH, THEN THE 60 AMP OCP IS IN VIOLATION OF 310.16 AND
 240.4.** SAME COMMENT REGARDING 5KW ON A 60 AMP
 BREAKER.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
 ANSWER REVIEW COMMENTS IN WRITING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]