| 2007-11-28 15:30:28 | RESIDENTIAL ADDITION BUILDING REVIEW THIRD CHECKLIST. |
| | REVIEW DONE UNDER EXISTING BUILDING CODE 2004, FLORIDA |
| | RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE COMPLETE SECTION/DETAIL AND SPECIFICATIONS |
| | SHOWING REINFORCEMENT AND SHORING SPECIFICATIONS FOR |
| | DEMOLITION OF EXTERIOR BEARING WALL AT BEDROOM#3 |
| | AREA.(NO REAR ROOM)(REPEAT COMMENT.THREE TIMES). |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. CONCERN WITH |
| | STRUCTURAL STABILITY OF BUILDING WHEN EXISTING BEARING |
| | WALL IS REMOVED AND ADDITIONAL ROOF LOAD WEIGHT IS |
| | ADDED WHEN RECEIVINGNEW ROOF.SEC. R301.1 OF 2004 |
| | FLORIDA RESIDENTIAL CODE. |
| | |
| | 2- ENGINEER TO PAY A FEE OF FOUR TIMES THE PLAN REVIEW |
| | FEES ($1308.30)AS REQUIRED BY FLORIDA STATUTE SEC. |
| | 553.80(2)(B). SEE ATTACHED FLORIDA STATUTE COPY. NOTE: |
| | ONE COPY OF PLANS WILL BE RETAINED IN THIS OFFICE. |
| | (NOTE: TALKED TO MR. ERVIN L. KEEL. SE SAID DRAWINGS |
| | WHERE SUBMITTED WITHOUT ENGINEER'S CONSENT) |
| | |
| | 3- ENERGY CALCULATIONS: SEE PLUMBING COMMENTS REGARDING |
| | WATER HEATER AND REVISE AS REQUIRED. (REPEAT COMMENT). |
| | |
| | 4- NOTICE OF COMMENCEMENT EXPIRES AFTER 90 DAYS OF |
| | BEING RECORDED IF WORK IS NOT STARTED.IT WAS RECORDED |
| | ON 08/14/2007, THEREFORE IS EXPIRED. NEED TO PROVIDE |
| | RE-RECORDED ONE. |
| | |
| | 5- SURVEY PROVIDED SHOWING 5.0' SIDE SETBACK IS NOT |
| | ACCURATE.THERE IS ANOTHER SURVEY SHOWING 4.4' |
| | SETBACK.THIS LOOKS LIKE EXISTING BUILDING IS AT 4.4' |
| | SETBACK.FLOOR PLANS SHOW NEW ADDITION BEING ALIGNED |
| | WITH EXISTING BUILDING. THEREFORE THE 5.0' SETBACK IS |
| | INCORRECT. NEED TO PROVIDE CORRECT INFORMATION. |
| | |
| | 6- SURVEY SUBMITTED STATES FLOOD ZONE "C". THIS |
| | PROPERTY IS LOCATED ON FLOOD ZONE "B". REVISE AS |
| | REQUIRED. |
| | NOTE: ONLY SURVEYOR IS ALLOWED TO DO REVISIONS ON HIS |
| | OWN WORK. |
| | |
| | 7- PREVIOUS SUBMITTAL INCLUDED SINGLE HUNG WINDOWS WITH |
| | IMPACT GLASS.PRODUCT APPROVAL SUBMITTED NOW IS FOR |
| | NON-IMPACT GLASS. THEREFORE SHUTTERS ARE REQUIRED. |
| | PRODUCT APPROVAL FOR STORM SHUTTERS SUBMITTED NEED MORE |
| | INFORMATION. NEED TO PROVIDE COMPLETE INSTALLATION |
| | SCHEDULE. SEE ATTACHED SAMPLE (OR PROVIDE COMPLETE |
| | INFORMATION ON ANOTHER FORMAT). ALSO, CLEARLY MARK ON |
| | SHUTTERS DRAWINGS SPECIFIC MOUNTING CONDITIONS (EG: |
| | WALL MOUNTED, BUILT OUT, ETC) AND SPECIFIC ANCHOR TYPE |
| | AND SPACING TO BE USED TO VERIFY COMPLIANCE WITH |
| | PROPOSED INSTALLATION. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 8- SHEET 1: |
| | A)DESIGN STANDARDS: WHAT'SCONSTRUCTION TYPE "E". |
| | WHERE IS THIS INFORMATION TAKEN FROM?. REVISE AS |
| | REQUIRED. |
| | |
| | B) ALSO, UPDATE THE FBC 2004 REVISIONS. CORRECT |
| | REVISIONSTO BE REFERENCED IS 2007, NOT 2006. REVISE |
| | AS REQUIRED. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |