Plan Review Notes
Plan Review Notes For Permit 07080417
Permit Number 07080417
Review Stop P
Sequence Number 2
Notes
Date Text
2007-10-17 11:08:18DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FBC-2004 WITH 05 & 06 REVISIONS, CHAPTER 13, ENERGY
 EFFICIENCY.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 THE RESUBMITTED PLUMBING PLAN REVIEW TO MEET CODE
 COMPLIANCE:
  
 1. SHEET 2, SANITARY RISER DIAGRAM: THE WASHING
 MACHINE AND SINK MUST DRAIN DOWNSTREAM OF THE WET
 VENTED BATHROOM GROUP PER FBC-2004 W/REV., PLUMBING,
 SECTION 909.1
 WET VENT PERMITTED: ONLY THE FIXTURES
 WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 2. SHEET 2, SANITARY RISER DIAGRAM: THE WASHING
 MACHINE IS "S" TRAPPED PER FBC-2004 W/REV., PLUMBING,
 SECTION 1002.3 "S" TRAPS ARE PROHIBITED.
  
 3. SHEET 2, SANITARY RISER DIAGRAM A CLEANOUT IS
 REQUIRED AT THE BASE OF THE WASTE STACK IN THE PROPOSED
 BATHROOM PER FBC-2004 W/REV., PLUMBING SECTION
 708.3.4.
  
 4. THE RESUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE
 FOR THE ADDITION DUE TO THE FACT THAT A WATER HEATER IS
 IN THE NEW ADDITION UTILITY ROOM AND THE ENERGY
 CALCULATIONS ARE INDICATINGPER (14) HOT WATER SYSTEM
 TYPE, N/A. PER THE FOLLOWING CHAPTER 13 ENERGY
 EFFICIENCY SECTION 13-101.0 GENERAL. THIS CODE IS A
 STATEWIDE UNIFORM CODE AND SHALL NOT BE MADE MORE
 STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE CODE
 PROVIDES FOR A UNIFORM STANDARD OF ENERGY EFFICIENCY
 BY, AT A MINIMUM, SETTING FORTH MINIMUM REQUIREMENTS
 FOR EXTERIOR ENVELOPES, LIGHTING, ELECTRICAL
 DISTRIBUTION, AND SELECTION OF HEATING, LIGHTING,
 VENTILATION, AIR CONDITIONING AND SERVICE WATER HEATING
 SYSTEMS. IT SHALL APPLY TO ALL NEW BUILDINGS, TO
 ADDITIONS TO EXISTING BUILDINGS AND MANUFACTURED HOMES,
 TO RENOVATIONS TO EXISTING BUILDINGS, BOTH PUBLIC AND
 PRIVATE, WITH CERTAIN EXCEPTIONS, TO CHANGES OF
 OCCUPANCY TYPE, TO THE SITE-INSTALLED COMPONENTS AND
 FEATURES OF A MANUFACTURED HOMES AT THEIR FIRST SET-UP,
 AND TO THE INSTALLATION OR REPLACEMENT OF BUILDING
 SYSTEMS AND COMPONENTS WITH NEW PRODUCTS FOR WHICH
 THERMAL EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW
 BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND
 IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF
 INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH
 SUBCHAPTER 13-4 OR 13-6 OF THIS CODE.
 NOTE: THE WATER HEATER IN THE NEW ADDITION UTILITY ROOM
 SHALL COMPLY PER THE FOLLOWING AND BE INDICATED ON THE
 RESUBMITTED ENERGY CALCULATIONS:
  
 A} 13-101.2.2 ADDITIONS.
 B} TABLE 13-612.1.ABC.3.2, MINIMUM PERFORMANCE
 STANDARDS, WATER HEATING EQUIPMENT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  
  
  