| 2007-10-17 11:08:18 | DENIED 2ND TIME |
| | REFERENCE: |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FBC-2004 WITH 05 & 06 REVISIONS, CHAPTER 13, ENERGY |
| | EFFICIENCY. |
| | ** FLORIDA ADMINISTRATIVE CODE (FAC). |
| | ** FLORIDA STATUTES (FS). |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | THE RESUBMITTED PLUMBING PLAN REVIEW TO MEET CODE |
| | COMPLIANCE: |
| | |
| | 1. SHEET 2, SANITARY RISER DIAGRAM: THE WASHING |
| | MACHINE AND SINK MUST DRAIN DOWNSTREAM OF THE WET |
| | VENTED BATHROOM GROUP PER FBC-2004 W/REV., PLUMBING, |
| | SECTION 909.1 |
| | WET VENT PERMITTED: ONLY THE FIXTURES |
| | WITHIN THE BATHROOM GROUPS SHALL CONNECT |
| | TO THE WET-VENTED HORIZONTAL BRANCH |
| | DRAIN. ANY ADDITIONAL FIXTURES SHALL |
| | DISCHARGE DOWNSTREAM OF THE WET VENT. |
| | |
| | 2. SHEET 2, SANITARY RISER DIAGRAM: THE WASHING |
| | MACHINE IS "S" TRAPPED PER FBC-2004 W/REV., PLUMBING, |
| | SECTION 1002.3 "S" TRAPS ARE PROHIBITED. |
| | |
| | 3. SHEET 2, SANITARY RISER DIAGRAM A CLEANOUT IS |
| | REQUIRED AT THE BASE OF THE WASTE STACK IN THE PROPOSED |
| | BATHROOM PER FBC-2004 W/REV., PLUMBING SECTION |
| | 708.3.4. |
| | |
| | 4. THE RESUBMITTED ENERGY CALCULATIONS ARE INCOMPLETE |
| | FOR THE ADDITION DUE TO THE FACT THAT A WATER HEATER IS |
| | IN THE NEW ADDITION UTILITY ROOM AND THE ENERGY |
| | CALCULATIONS ARE INDICATINGPER (14) HOT WATER SYSTEM |
| | TYPE, N/A. PER THE FOLLOWING CHAPTER 13 ENERGY |
| | EFFICIENCY SECTION 13-101.0 GENERAL. THIS CODE IS A |
| | STATEWIDE UNIFORM CODE AND SHALL NOT BE MADE MORE |
| | STRINGENT OR LENIENT BY LOCAL GOVERNMENT. THE CODE |
| | PROVIDES FOR A UNIFORM STANDARD OF ENERGY EFFICIENCY |
| | BY, AT A MINIMUM, SETTING FORTH MINIMUM REQUIREMENTS |
| | FOR EXTERIOR ENVELOPES, LIGHTING, ELECTRICAL |
| | DISTRIBUTION, AND SELECTION OF HEATING, LIGHTING, |
| | VENTILATION, AIR CONDITIONING AND SERVICE WATER HEATING |
| | SYSTEMS. IT SHALL APPLY TO ALL NEW BUILDINGS, TO |
| | ADDITIONS TO EXISTING BUILDINGS AND MANUFACTURED HOMES, |
| | TO RENOVATIONS TO EXISTING BUILDINGS, BOTH PUBLIC AND |
| | PRIVATE, WITH CERTAIN EXCEPTIONS, TO CHANGES OF |
| | OCCUPANCY TYPE, TO THE SITE-INSTALLED COMPONENTS AND |
| | FEATURES OF A MANUFACTURED HOMES AT THEIR FIRST SET-UP, |
| | AND TO THE INSTALLATION OR REPLACEMENT OF BUILDING |
| | SYSTEMS AND COMPONENTS WITH NEW PRODUCTS FOR WHICH |
| | THERMAL EFFICIENCY STANDARDS ARE SET BY THIS CODE. NEW |
| | BUILDINGS, WITH EXCEPTION OF THOSE EXEMPTED BELOW, AND |
| | IN ACCORDANCE WITH THE SPECIFIC EXCEPTIONS OF |
| | INDIVIDUAL SECTIONS SHALL BE DESIGNED TO COMPLY WITH |
| | SUBCHAPTER 13-4 OR 13-6 OF THIS CODE. |
| | NOTE: THE WATER HEATER IN THE NEW ADDITION UTILITY ROOM |
| | SHALL COMPLY PER THE FOLLOWING AND BE INDICATED ON THE |
| | RESUBMITTED ENERGY CALCULATIONS: |
| | |
| | A} 13-101.2.2 ADDITIONS. |
| | B} TABLE 13-612.1.ABC.3.2, MINIMUM PERFORMANCE |
| | STANDARDS, WATER HEATING EQUIPMENT. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |