| 2007-10-17 14:57:41 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA |
| | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES |
| | (F.S.). |
| | |
| | *** DENIED *** |
| | 1) PLANS SHOW TOTAL AREA UNDER AIR AT 1,818 SQUARE |
| | FEET, COOLING LOAD CALCULATIONS SHOW ROOF AREA AT 2118 |
| | IS THAT SQUARE FEET OR BTU'S, PLEASE SUBMIT LONG FORM |
| | CALCULATIONS AS REQUIRED BY 2004 FBC/R M1401.3 HEATING |
| | AND COOLING EQUIPMENT SHALL BE SIZED BASED ON BUILDING |
| | LOADS CALCULATED IN ACCORDANCE WITH ACCA MANUAL J OR |
| | OTHER APPROVED HEATING AND COOLING CALCULATION |
| | METHODOLOGIES. |
| | |
| | 2)ENERGY CALCULATIONS NEED TO BE SIGNED BY |
| | OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2. |
| | |
| | 3) MECHANICAL PLAN SUBMITTED HAVE TO MUCH FLOOR PLAN |
| | DETAIL ON THEM AND DUCT DESIGN IS FADED THEY ARE |
| | DIFFICULT TO READ.CONSTRUCTION DOCUMENTS SHALL BE OF |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, SEE F.B.C. 106.1.1. |
| | |
| | 4) WHEN RESUBMITTING MECHANICAL PLANS PLEASE HAVE THEM |
| | APPEAR SEMI-PROFESSIONAL AND HAVE ALL PERTINENT |
| | INFORMATION ON THEM (JOB ADDRESS, DESIGNER'S |
| | INFORMATION & SIGNATURE, EQUIPMENT SCHEDULE, ETC. |
| | |
| | 5) MECHANICAL PLAN SHOWS A 16' SUPPLY AND A 18" RETURN |
| | DUCT GOING OFF THE PAGE, PLEASE SHOW WERE THEY ARE |
| | GOING. |
| | |
| | 6) RETURN AIR WILL BE NEEDED IN BEDROOM #4, SEE 2004 |
| | FBC/R M1602.4. |
| | |
| | 7) BUILDING AND ELECTRICAL PLAN SHOW THE A/C CONDENSER |
| | UNIT IN A DIFFERENT LOCATION THEN THE MECHANICAL PLAN |
| | DOES, PLEASE CORRECT. |
| | |
| | 8) SHOW LOCATION OF THE CLOTHES DRYER VENT ON THE |
| | MECHANICAL PLAN, BE ADVISED THE CLOTHES DRYER VENT MAY |
| | NOT DISCHARGE NEAR THE A/C CONDENSER UNIT, SEE 2004 |
| | FBC/R 401.5.2 |
| | |