| 2007-10-11 13:05:05 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 |
| | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH |
| | THE FOLLOWING: |
| | THE FOLLOWING COMMENTS ARE REGARDING THE ELECTRICAL |
| | DRAWINGS ON SHEET 2 OF 2. |
| | |
| | THESE COMMENTS WERE NOT ADDRESSED ON THE PREVIOUS |
| | REVIEW, 8/27/07. |
| | |
| | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION |
| | ON THE APPLICATION, PROVIDE AN AIC RATING, ANDLOCATE |
| | ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, |
| | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER |
| | DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE.* THE |
| | AIC RATING IS NOT ON THE PLAN. |
| | |
| | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC |
| | AS AMENDED. THERE IS NO CONDENSER # 2 ON THE SCHEDULE |
| | PROVIDED AND APPLIANCES THAT ARE IN THE CALCULATION ARE |
| | MISSING. SEE 408.4 2005 NEC. *THERE ARE STILL |
| | APPLIANCES MISSING FROM THE SCHEDULE. SMALL APPLIANCE, |
| | WASHER AND THE TERMS "CONV. OUTLETS AND GEN LIGHTING" |
| | ARE NOT SPECIFIC ENOUGH TO MEET THE INTENT OF 408.4. |
| | |
| | 3} THERE IS 10000 VA OF HEAT IN THE LOAD CALCULATION, |
| | CORRECTLY CALCULATED AT 100% PER 220.83(B), BUT THE |
| | PANEL SCHEDILE INDICATES 2 AIR HANDLERS WITH AN OCP OF |
| | 60 AMPS, WHICH WOULD IMPLY THAT THERE ARE 2 UNITS WITH |
| | 10000 VA EACH. PLEASE CLARIFY. *IF THE AHU'S ARE 5KW |
| | EACH, THEN THE 60 AMP OCP IS IN VIOLATION OF 310.16 AND |
| | 240.4. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. |
| | ANSWER REVIEW COMMENTS IN WRITING. |
| | |