2007-10-19 13:31:50RESIDENTIALADDITION BUILDING REVIEW SECOND
 CHECKLIST.
 REVIEW DONE UNDER EXISTING BUILDING CODE 2004,
 RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007
 REVISIONS.
  
 1- VALUE DECLARED IN THE PERMIT APPLICATION IS TOO LOW.
 OWES $320.93 FOR UPDATED VALUATION AND RADON FEES.
 (REPEAT COMMENT).
 RESPONSE LETTER SAID FEES WERE PAID AND PAID RECEIPT IS
 ATTACHED.THIS WAS NOT DONE.
  
 2- PROVIDE COMPLETE SECTION/DETAIL AND SPECIFICATIONS
 SHOWING REINFORCEMENT AND SHORING SPECIFICATIONS FOR
 DEMOLITION OF EXTERIOR BEARING WALL AT BEDROOM #3 AREA.
 (REPEAT COMMENT). SEC. 106.1.2 CITY AMENDMENTS TO FBC
 2004.
 PLANS DON'T SHOW ANY DETAILS OR SPECIFICATIONS SHOWING
 HOW TO SHORE STRUCTURE TO AVOID COLLAPSE OF ROOF ABOVE
 WHEN WALL IS REMOVED.
  
 3- PLANS TO SPECIFY ALL LIVE AND DEAD LOADS, INCLUDING
 THE ATTIC LIVE LOADS. ENGINEER TO REVIEWSEC. R301 AND
 TABLE R301.5 OF RESIDENTIAL CODE 2004 AND PROVIDE
 REQUIRED INFORMATION. (REPEAT COMMENT). INFORMATION
 SUBMITTED IS INCOMPLETE AND INCORRECT. IT CAN'T BE ONLY
 10PSF ATTIC LIVE LOAD AND DEAD LOAD OF 30PSF. REVISE
 DESIGN INFORMATION AS REQUIRED.
  
 4- ENGINEER TO REVIEW ATTACHED COPY OF FLORIDA STATUTE
 553.80(2)(B) REGARDING PLAN REVIEW FEES TO BE PAID BY
 ENGINEER WHEN DOCUMENTS ARE REJECTED SEVERAL TIMES.
 ***NOTE: ONE COPY OF PLANS WILL BE RETAINED IN THIS
 OFFICE TO BE SEND TOFLORIDA BOARD OF ENGINEERS FOR
 REVIEW.
  
 5- ENERGY CALCULATIONS:
 A) SEE PLUMBING COMMENTS REGARDING WATER HEATER.
  
 B) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM.
  
 6- SOIL TEST REPORT CALLS FOR 2000 PSF SOIL BEARING
 CAPACITY, WHILE STRUCTURAL NOTE #1 ONSHEET 2 REQUIRES
 2500 PSF SOIL BEARING CAPACITY.ACCORDING TO THIS THE
 SOIL DOESN'T MEET THE ENGINEER'S DESIGN CRITERIA.
 REVISE AS REQUIRED.
  
 7- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE
 9B-72 FOR:
 A) SINGLE HUNG WINDOWS. NEED TO PROVIDEREPORT WITH
 LEGIBLE DRAWINGS AS REQUIRED BY SEC. 106.1.3 CITY
 AMENDMENTS TO FBC 2004. (REPEAT COMMENT).
  
 B) ALL SIMPSON STRUCTURAL CONNECTORS SPECIFIED ON
 ALL PLANS. (REPEAT COMMENT).
 ONLY PRODUCT APPROVAL FOR ONE CONNECTOR WAS SUBMITTED.
  
 ***NOTE: CLARIFY WHY SUBMITTING PRODUCT APPROVAL FOR
 STORM SHUTTERS IF WINDOWS PRODUCT APPROVALSUBMITTED
 HAVE MISSILE IMPACT GLASS.
  
 8- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING
 (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS
 REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004.
 (REPEAT COMMENT).
 ENGINEER CAN'T SIGN AND SEAL THESE PRODUCT APPROVALS
 BECAUSE THEY ARE NOT HIS DESIGN.
 PLEASE MAKE SURE NAME OF ENGINEER APPROVING PRODUCT
 APPROVALS IS SHOWN ON THE REVIEW PRODUCT APPROVAL.
  
 9- REVISE ROOF SHEATHING NAILING SPACING. SEE SEC.
 R803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE.REPEAT
 COMMENT.NEED TO IDENTIFY ROOF ZONE 3 AND NAIL SPACING
 AS REQUIRED BY THE CITE SECTION ON THIS COMMENT.
  
 10- PLEASE DON'T STAPLE PRODUCT APPROVALS TO THE
 DRAWINGS. THIS WILL EXPEDITE THE REVIEW PROCESS.
  
 11- TYPICAL WALL SECTION. REVISE CEILING INSULATION
 VALUE TO MATCH THE ENERGY CALCULATIONS.
  
 ***NOTE:RE-SUBMITTAL FEES WILL APPLY FOR NEXT
 SUBMITTAL.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER