Plan Review Notes
Plan Review Notes For Permit 07080417
Permit Number 07080417
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-06 08:46:08DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING WITH 2006 REVISIONS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SHEET 2 PLUMBING RISER DIAGRAM: THE WASHING MACHINE
 BRANCH DRAIN, DRAINAGE STACK ANDTRAP ARE SIZED WRONG
 PER FBC-2004 PLUMBING WITH 2006 REVISIONS PER THE
 FOLLOWING CODE SECTIONS. PLEASE CORRECT AND RESUBMIT.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING. PLEASE INDICATE THE WASHING MACHINE
 STANDPIPE ON THE RESUBMITTAL.
  
 2. SHEET 2 PLUMBING RISER DIAGRAM: THE WASHING MACHINE
 AND SINK IN THE UTILITY ROOM MUST DISCHARGE DOWNSTREAM
 OF THE PROPOSED WET VENTED BATHROOM PER FBC-2004
 PLUMBING WITH 2006 REVISIONS FOLLOWING CODE SECTION.
 PLEASE CORRECT AND RESUBMIT.
  
 (A) SECTION 909.1 WET VENT PERMITTED: ONLY THE
 FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT TO
 THE WET-VENTED HORIZONTAL BRANCH
 DRAIN. ANY ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT.
 NOTE: WHERE THE PROPOSED 3 INCH TO THE EXISTING
 SANITARY SYSTEM IS INDICATED IT ALSO MUST DISCHARGE
 DOWNSTREAM OF THE EXISTING WET VENTED BATHROOMS. PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 3. SHEET 2 PLUMBING RISER DIAGRAM: PER FBC-2004
 PLUMBING WITH 2006 REVISIONS SECTION 708.3.4 BASE OF
 STACK. A CLEANOUT SHALL BE PROVIDED AT THE BASE OF EACH
 WASTE OR SOIL STACK. PLEASE CORRECT AND RESUBMIT.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK
 ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR
 REFERENCE FOR THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER