Plan Review Notes
Plan Review Notes For Permit 07080417
Permit Number 07080417
Review Stop M
Sequence Number 1
Notes
Date Text
2007-08-29 13:40:33PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA
 ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS).
  
 *** DENIED ***
 1) SUBMIT ENERGY CALCULATIONS PER 2004 FBC 13-101.2.2.
  
 2) SUBMIT COOLING LOAD CALCULATIONS PER 2004 FBC
 13-607.1.ABC.1.
  
 3) MECHANICAL PERMIT #07080419 HAS BEEN APPLIED FOR AND
 BUILDING PLANS SHOW AN A/C SYSTEM TO BE INSTALLED BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  