 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004
 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH
 THE FOLLOWING:
 THE FOLLOWING COMMENTS ARE REGARDING THE ELECTRICAL
 DRAWINGS ON SHEET 2 OF 2.
  
 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN
 IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION
 ON THE APPLICATION, PROVIDE AN AIC RATING, ANDLOCATE
 ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE,
 DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH
 ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER
 DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE.
  
 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT
 BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT
 PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC
 AS AMENDED. THERE IS NO CONDENSER # 2 ON THE SCHEDULE
 PROVIDED AND APPLIANCES THAT ARE IN THE CALCULATION ARE
 MISSING. SEE 408.4 2005 NEC.
  
 3} THERE IS 10000 VA OF HEAT IN THE LOAD CALCULATION,
 CORRECTLY CALCULATED AT 100% PER 220.83(B), BUT THE
 PANEL SCHEDILE INDICATES 2 AIR HANDLERS WITH AN OCP OF
 60 AMPS, WHICH WOULD IMPLY THAT THERE ARE 2 UNITS WITH
 10000 VA EACH. PLEASE CLARIFY.
  
 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE
 PER 210.11(C) (3),THIS CIRCUIT IS NOT ON THE
 SCHEDULE.
  
 5} R313.1.1, RESIDENTIAL BUILDING CODE, SMOKE ALARMS
 SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN
 REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE
 ARTICLE FOR COMPLETE TEXT.ALSO SEE THE DEFINITION OF
 "SMOKE DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING
 DETECTORS OR ALARMS, TO AVOID CONFUSION IN THE FIELD.
 IF USING DETECTORS INDICATE THE LOCATIONS OF THE
 SOUNDING DEVICES.
  
 6} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER.
 SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND
 422.31(B) FOR HARDWIRE REQUIREMENTS. ALSO 110.26 AND
 440.14 FOR THE CONDENSING UNIT.
  
 PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH
 CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM
 SEPARATELY TO EXPEDITE THE REVIEW PROCESS.
 ANSWER REVIEW COMMENTS IN WRITING.
  