| 2007-08-27 10:19:17 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, 2004 |
| | FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH |
| | THE FOLLOWING: |
| | THE FOLLOWING COMMENTS ARE REGARDING THE ELECTRICAL |
| | DRAWINGS ON SHEET 2 OF 2. |
| | |
| | 1} INDICATE IF THE ELECTRICAL SERVICE SHOWN ON THE PLAN |
| | IS NEW OR EXISTING. IF NEW INCLUDE IN THE DESCRIPTION |
| | ON THE APPLICATION, PROVIDE AN AIC RATING, ANDLOCATE |
| | ALL SERVICE EQUIPMENT ON THE PLAN, METER ENCLOSURE, |
| | DISCONNECTS AND PANELS, SO THAT COMPLIANCE WITH |
| | ARTICLES 225 AND 230 CAN BE REVIEWED. PROVIDE A RISER |
| | DIAGRAM WITH CONDUCTOR AND CONDUIT SIZE AND TYPE. |
| | |
| | 2} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC |
| | AS AMENDED. THERE IS NO CONDENSER # 2 ON THE SCHEDULE |
| | PROVIDED AND APPLIANCES THAT ARE IN THE CALCULATION ARE |
| | MISSING. SEE 408.4 2005 NEC. |
| | |
| | 3} THERE IS 10000 VA OF HEAT IN THE LOAD CALCULATION, |
| | CORRECTLY CALCULATED AT 100% PER 220.83(B), BUT THE |
| | PANEL SCHEDILE INDICATES 2 AIR HANDLERS WITH AN OCP OF |
| | 60 AMPS, WHICH WOULD IMPLY THAT THERE ARE 2 UNITS WITH |
| | 10000 VA EACH. PLEASE CLARIFY. |
| | |
| | 4} BATH CIRCUIT REQUIRED TO HAVE A 20 AMP RECEPTACLE |
| | PER 210.11(C) (3),THIS CIRCUIT IS NOT ON THE |
| | SCHEDULE. |
| | |
| | 5} R313.1.1, RESIDENTIAL BUILDING CODE, SMOKE ALARMS |
| | SHALL BE LOCATED AS REQUIRED IN NEW DWELLINGS WHEN |
| | REPAIRS OR ADDITIONS REQUIRING A PERMIT OCCUR. SEE |
| | ARTICLE FOR COMPLETE TEXT.ALSO SEE THE DEFINITION OF |
| | "SMOKE DETECTORS" 11.8.2.1 NFPA-72, CLARIFY IF USING |
| | DETECTORS OR ALARMS, TO AVOID CONFUSION IN THE FIELD. |
| | IF USING DETECTORS INDICATE THE LOCATIONS OF THE |
| | SOUNDING DEVICES. |
| | |
| | 6} INDICATE A DISCONNECTING MEANS FOR THE WATER HEATER. |
| | SEE 422.16 NEC FOR CORD AND PLUG RESTRICTIONS, AND |
| | 422.31(B) FOR HARDWIRE REQUIREMENTS. ALSO 110.26 AND |
| | 440.14 FOR THE CONDENSING UNIT. |
| | |
| | PLEASE REMOVE ALL OLD OR VOIDED SHEETS AND REPLACE WITH |
| | CORRECTED ONES WHEN RESUBMITTING. INCLUDE THEM |
| | SEPARATELY TO EXPEDITE THE REVIEW PROCESS. |
| | ANSWER REVIEW COMMENTS IN WRITING. |
| | |