| 2007-09-06 14:01:25 | RESIDENTIAL ADDITION BUILDING REVIEW FIRST CHECKLIST. |
| | REVIEW DONE UNDER 2004 FLORIDA RESIDENTIAL CODE AND |
| | FBC 2004 WITH 2007 REVISIONS. |
| | |
| | 1- AFTER PLANS ARE REVISED, BRING THEM TO PALM BEACH |
| | COUNTY (2300 N. JOG RD (561)233-5115)TO VERIFY IF |
| | IMPACT FEES ARE DUE OR NOT. BRING BACK STAMPED PLANS |
| | AND COPY OF PAID RECEIPT IF FEES ARE DUE. |
| | |
| | 2- VALUEDECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW.VALUE WAS UPDATED TO $59,025 AS REQUIRED BY SEC. |
| | 108.3 OF CITY AMENDMENTS TO FBC 2004. THEREFORE, OWES |
| | $320.93 FOR UPDATED VALUATION AND RADON FEES. |
| | |
| | 3- FLOOR PLAN SHOWS ACCESS TOBEDROOM #5 THRU BEDROOM |
| | #4. GOING FROM ONE ROOM BEDROOM THRU ANOTHER BEDROOM IS |
| | NOT ALLOWED BY SEC. 1013.2 FBC 2004. REVISE AS |
| | REQUIRED. |
| | |
| | 4- ENGINEER TO PROVIDE HIS FIRM CERTIFICATE OF |
| | AUTHORIZATION NUMBER IN THE TITLE BLOCK AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE AND SEC. 61G15--23.002 OF |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | 5- PLANS TO SPECIFY CONSTRUCTION TYPE AS REQUIRED BY |
| | SEC. 602.1 FBC 2004. |
| | |
| | 6- PROVIDE COMPLETE SECTION/DETAIL AND SPECIFICATIONS |
| | SHOWING REINFORCEMENT AND SHORING SPECIFICATIONS FOR |
| | DEMOLITION OF EXTERIOR BEARING WALL AT BEDROOM #3 AREA. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 7- SPECIFY ATTIC ACCESS AS REQUIRED BY SEC. R807 OF |
| | 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 8- PLANS TO SPECIFY ALLLIVE AND DEAD LOADS, INCLUDING |
| | THE LIVE LOADINTHE ATTIC AS REQUIRED BYTABLE |
| | R301.5 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- DRAWINGS ARE NOT LEGIBLE.LETTERING ON SOME DETAILS |
| | IS NOT LEGIBLE. MAKE SURE ALL DETAILS AND NOTES ARE |
| | CLEAR AND LEGIBLE AS REQUIRED BY SEC. 106.1.3 OF CITY |
| | AMENDMENTS TO FBC 2004.. |
| | |
| | 10- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.1.C.1 FBC 2004. |
| | NOTE: MAKE SURE CORRECT 2006 REVISED FORM IS USED. AND |
| | MAKE SURE FORM IS FILLED COMPLETELY AND SIGNED AND |
| | DATED BY THE PREPARER AND OWNER. |
| | |
| | 11- PROVIDE 2 COPIES OF SOIL TEST REPORT AS REQUIRED BY |
| | SEC. R401.4 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |
| | 12- PRECAST CONCRETE LINTEL SCHEDULE TO BE KEYED ON |
| | PLANS TO VERIFY SIZES. SEC. 106.1.2 CITY AMENDMENTS TO |
| | FBC 2004. |
| | |
| | 13- PROVIDE PRODUCT APPROVAL AS REQUIRED BY DCA RULE |
| | 9B-72 FOR: |
| | A) EXTERIOR DOORS. PROVIDE COMPLETE REPORT SHOWING |
| | ALL TECHNICAL INFORMATION FOR MODEL TO BE INSTALLED. |
| | ONLY FLORIDA FL4904 PRODUCT COVER PAGES WERE |
| | SUBMITTED. |
| | |
| | B) SINGLE HUNG WINDOWS. PROVIDE LEGIBLE DRAWINGS. |
| | NOA 03-0910.04 SUBMITTED IS NOT LEGIBLE. SEC. 106.1.3 |
| | CITY AMENDMENTS TO FBC 2004. |
| | |
| | C) STORM PANELS. PROVIDE LEGIBLE DRAWINGS. SEC. |
| | 106.1.3 CITY AMENDMENTS TO FBC 2004. |
| | ***NOTE: PROVIDECOMPLETE INSTALLATION SCHEDULE. SEE |
| | ATTACHED SAMPLE. AND, CLEARLY INDICATE ON SHUTTERS |
| | DRAWINGS SPECIFIC ANCHOR TYPE AND SPACING TO BE USED. |
| | SEC. 106.1.2 CITY AMENDMENTS TO FBC 2004. |
| | |
| | D) ALL SIMPSON CONNECTORS SPECIFIED ON PLANS AND |
| | DETAILS. |
| | ***NOTE: PROVIDE ONLY THE FLORIDA PRODUCT APPROVAL |
| | COVER PAGE AND PAGE WERE CONNECTOR IS SHOWN. |
| | |
| | E) PRECAST LINTELS SPECIFIED ON PLANS. |
| | |
| | 14- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC 2004. |
| | |
| | 15- SHEET 2: |
| | A) SPECIFY CONNECTOR AT BOTH ENDS OF GIRDER TRUSS |
| | SHOWN BY BEDROOM #3ROOF AREA. SEC. 106.1.2 CITY |
| | AMENDMENTS TO FBC 2004. |
| | |
| | B) REVISE ATTACHMENT SCHEDULE. CLARIFY WHYSOME |
| | CONNECTORS THE ENGINEER IS USING THE 133 VALUES AND |
| | SOME CONNECTORS THE 160 VALUE.. EG SEE MTS16 |
| | CONNECTOR. |
| | |
| | C) REVISE ROOF SHEATHING NAILING SPACING . SEE SEC. |
| | 803.2.3.1 OF 2004 FLORIDA RESIDENTIAL CODE FOR MIN. |
| | REQUIRED SPACING INCLUDING NAILING AT CORNER ZONE #3 |
| | AREAS. |
| | |
| | D) REVISE DOOR AND WINDOW ATTACHMENT NOTES. SEE |
| | CORRESPONDING PRODUCT APPROVALS FOR REQUIRED FASTENER |
| | TYPE SIZE AND SPACING. ALSO, VERIFY SUBSTRATE TO BE |
| | INSTALLED TO. |
| | |
| | JULIO GOMEZ |
| | BUILDING PLANS EXAMINER |
| | (561)805-6712 |