| Date |
Text |
| 2008-10-03 15:50:43 | |
| | ** DENIED 4TH REVIEW ** |
| | 3RD REVIEW UNDER PERMIT APPLICATION. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED FORM *C* IS NOT IN |
| | COMPLIANCE WITH FBC 13-415.2,13-415.2.ABC.1.1,.1.2, |
| | .1.3. |
| | THE FORM *C* NOW NOTES THREE SEPARATE SPACES WHICH MAY |
| | NOT BE USED AS FORM *C* IS FOR A SPECIFIC USE OR |
| | OCCUPANCY. IF USING A SPACE BY SPACE THEN TABLE *B* IS |
| | REQUIRED TO BE USED. PLEASE SEE THE SECTIONS ABOVE |
| | ALONG WITH SECTION 202 OF CHAPTER 13 FOR THE |
| | DEFINITIONS OF A RENOVATION. THE FORM *C* DOES NOT SHOW |
| | COMPLIANCE FOR EXTERIOR LIGHTING AS NOTED IN |
| | 13-415.2.ABC.1.3 NOTED INALL REVIEWS. |
| | COMPLIANCE WITH THE SPECIFIC CODES ABOVE HAS NOT BEEN |
| | DEMONSTRATED. THE RESPONSE LETTER MENTIONS THIS IS NOT |
| | AN ELECTRICAL COMMENT. HOWEVER PLEASE SEE STATEMENTS |
| | ISSUED BY THE FLORIDA BUILDING COMMISSION WHICH ARE |
| | AVAILABLE ON-LINE WHICH STATE: * THE INTENT FOR REVIEW |
| | OF THE CALCULATIONS AND CHAPTER 13 IS FOR EACH TRADE |
| | REVIEWER TO REVIEW THAT PARTICULAR TRADE. |
| | A CALLED WAS PLACED TO THE ELECTRICAL ENGINEER AS OF |
| | THIS REVIEW AND A MESSAGE WAS LEFT ON VOICEMAIL TO |
| | RETURN CALL. |
| | THE CALCULATIONS ON FORM *C* AS SUBMITTED ALONG WITH |
| | ELECTRICAL PLANS WILL BE RETAINED BY THIS OFFICE. |
| | BASED ON THE *C* SUBMITTED AND OCCUPANCY DESIGN WATTAGE |
| | IS OVER THE ALLOWANCES PERMITTED. THIS IS NOT |
| | LODGE/HOTEL/TRANSIENT LODGING. THIS IS A ASSEMBLY |
| | OCCUPANCY BASED ON ARCHITECTURAL PLANS OCCUPANCY |
| | DESIGNATION. PLEASE CONTACT THIS OFFICE/REVIEW TO GO |
| | OVER HOWEVER THE CODE COMPLIANCE CAN BE SHOWN. |
| | |
| | |
| | 2) NOTE: PLEASE SEE THE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENT FOR CODE COMPLIANCES. THE SPECIFIC |
| | SECTIONS OF THE CODE HAVE BEEN GIVEN NOW FOR FOUR |
| | REVIEWS THREE OF WHICH ARE UNDER PERMIT APPLICATION. |
| | THE STATUTORY REQUIREMENT IS THAT A FEE BE ASSESSED. |
| | THIS IS NOT A LOCAL ORDINANCE, REGULATION, OR |
| | ADMINISTRATIVE AMENDMENT. THIS IS A FLORIDA STATUTE |
| | REQUIRED FEE. THIS OFFICE HAS PLACED THE CONTACT |
| | INFORMATION FOR ANY QUESTIONS OR COMMENTS ON ALL |
| | REVIEWS TO GO OVER PLANS HOWEVER CONTACT HAS NOT YET |
| | BEEN MADE. |
| | |
| | |
| | |
| | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT |
| | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO |
| | CONTACT THIS REVIEWER. |
| | |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPARTMENT |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |