| 2008-04-25 10:00:24 | REVIEW #: 3RD |
| | ACTION: DENIED |
| | |
| | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH |
| | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN |
| | RESPONSES FOR THE PURPOSE OF CONTINUITY. |
| | |
| | COMMENTS 1-4 OK |
| | |
| | 5. FRC SECTION M1501.1 EXCEPTION 1: "WHERE A CLOTHES |
| | DRYER BOOSTER FAN IS INSTALLED AND LISTED AND LABELED |
| | FOR THE APPLICATION, THE MAXIMUM LENGTH OF THE EXHAUST |
| | DUCT, INCLUDING ANY TRANSITION DUCT, SHALL BE PERMITTED |
| | TO BE IN ACCORDANCE WITH THE BOOSTER FAN MANUFACTURER?S |
| | INSTALLATION INSTRUCTIONS." |
| | NO DRYER BOOSTER FAN LISTING OR INSTALLATION |
| | INSTRUCTIONS HAVE BEEN PROVIDED. NOTE THAT THIS SECTION |
| | REQUIRES THE BOOSTER FAN TO BE LISTED FOR USE IN A |
| | DOMESTIC CLOTHES DRYER APPLICATION. IF THIS EXCEPTION |
| | IS TO BE USED, PROVIDE ALL REQUIRED INFORMATION TO BE |
| | INCLUDED IN THE PERMIT DOCUMENTATION PRIOR TO PERMIT |
| | ISSUANCE. |
| | FRC SECTION M1501.1 EXCEPTION 2: "WHERE THE MAKE AND |
| | MODEL OF THE CLOTHES DRYER TO BE INSTALLED IS KNOWN AND |
| | THE MANUFACTURER?S INSTALLATION INSTRUCTIONS FOR SUCH |
| | DRYER ARE PROVIDED TO THE BUILDING OFFICIAL, THE |
| | MAXIMUM LENGTH OF THE EXHAUST DUCT, INCLUDING ANY |
| | TRANSITION DUCT, SHALL BE PERMITTED TO BE IN ACCORDANCE |
| | WITH THE DRYER MANUFACTURER?S INSTALLATION |
| | INSTRUCTIONS." |
| | NO DRYER MODEL OR INSTALLATION INSTRUCTIONS HAVE BEEN |
| | PROVIDED. IF THIS EXCEPTION IS TO BE USED, PROVIDE ALL |
| | REQUIRED INFORMATION TO BE INCLUDED IN THE PERMIT |
| | DOCUMENTATION PRIOR TO PERMIT ISSUANCE. |
| | |
| | NOTE: THE CLOTHES DRYER SHALL BE INSTALLED AND |
| | TRANSITION DUCT CONNECTED FOR FINAL MECHANICAL |
| | INSPECTION. |
| | |
| | NOTE: PLEASE ADDRESS ELECTRICAL REVIEW COMMENTS RELATED |
| | TO ELECTRICAL RATINGS OF A/C APPLIANCES, SHOWING |
| | COORDINATION BETWEEN MANUFACTURER'S REQUIREMENTS, |
| | ELECTRICAL PLANS AND A/C UNIT SCHEDULE ON PG AC-2. |
| | |
| | ALL OTHER MECHANICAL COMMENTS HAVE BEEN ADEQUATELY |
| | ADDRESSED. |
| | |