| 2008-04-03 18:43:28 | ** DENIED 3RD REVIEW ** |
| | ** ONLY 2ND REVIEW UNDER ACTUAL PERMIT APPLICATION. |
| | |
| | ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEW ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | COMMENTS BASED ON CHANGES MADE TO PLANS AND/OR |
| | DOCUMENTS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS |
| | FOR COMMERCIAL PORTION OF BUILDING NEEDS TO MEET CODE |
| | AND COORDINATE WITH PLANS. PLEASE BE SURE TO SEE |
| | 13-415.2, 13-415.2.ABC.1.1, .1.2 AND .1.3. |
| | FOR EXAMPLE: |
| | PLEASE BE SURE TO SEE THE CALCULATIONS STATED ON SHEET |
| | E-3 STATES THIS BUILDING AS A "LODGE". HOW IS THIS |
| | POSSIBLE? THE SUBMITTED ENERGY CALCULATIONS CLEARLY |
| | STATE "OFFICE". |
| | FOR EXAMPLE: |
| | PLEASE SEE THE INPUT DATA REPORT WHICH DOES NOT SHOW |
| | ANY EXTERIOR LIGHT FIXTURES YET THE PLANS CLEARLY SHOW |
| | EXTERIOR LIGHTING. HOW IS THIS POSSIBLE? |
| | FOR EXAMPLE: |
| | PLEASE SEE ONLY TWO TYPES OF FIXTURES ARE SHOWN FOR |
| | FIRST FLOOR ZONE HOWEVER THE PLANS CONTAINS A MINIMUM |
| | OF FOUR DIFFERENT TYPES OF FIXTURES. (THIS IS NOT |
| | NOTING THE SEPARATE ELEVATOR ZONE) |
| | FOR EXAMPLE: |
| | PLEASE SEE UPPER FLOOR ZONE FOR AHU3. WHERE ARE K |
| | FIXTURES, WHERE ARE THE FIXTURES IN BATHROOMS SHOWN FOR |
| | SHOWERS? WHERE ARE THE WALL SCONCES? |
| | |
| | ** PLEASE ALSO BE SURE THE OWNER AGENT IS SIGNED ON THE |
| | CERTIFICATION SHEET WHEN RESUBMITTING. FBC 13-103.1 |
| | |
| | 2) NOTE: PLEASE SEE THE TAPPED CONDUCTORS FROM THE |
| | 320AMP METER CAN SHALL TERMINATE IN OVER CURRENT |
| | PROTECTION HOWEVER THE RISER ONLY SHOWS A 30AMP 2-POLE |
| | DISCONNECT AT BOTH THE SERVICE MAIN LOCATION AND THE |
| | ELEVATOR DISCONNECT. |
| | PLEASE KNOW THE FIRST ITEM IS THIS 30AMP DISCONNECT IS |
| | ONE OF THE SERVICE MAINS YET NO LABELING OF THIS IS |
| | SHOWN. 230.2E (ALL) |
| | PLEASE SEE THE SECOND ITEM IS THAT THIS 30AMP |
| | DISCONNECT SHALL BE SERVICE EQUIPMENT RATED AND SERVICE |
| | ENTRANCE RATED FOR A MAIN. 230.70, 230.71, 110.7, 90.7 |
| | PLEASE VERIFY THIS. |
| | PLEASE SEE FOR THE THIRD ITEM; PLEASE SEE 240.21, |
| | 310.16 AND 240.4 AS THE TAPPED CONDUCTORS SHALL |
| | TERMINATE IN OVER CURRENT PROTECTION. |
| | |
| | 3) NOTE: PLEASE SEE THE OVER CURRENT PROTECTION SHOWN |
| | ON ELECTRICAL PANEL SCHEDULES AND MECHANICAL PLANS ARE |
| | NOT CODE COMPLIANT. |
| | PLEASE SEE THE CODE REQUIRES MINIMUM OVER CURRENT |
| | PROTECTION OF 125% PER 424.3B. PLEASE SEE ONE OF THE |
| | 5KW AH UNITS STATES 60AMP OCP. |
| | PLEASE SEE THE AC SHEETS AS THESE STATES THE MINIMUM |
| | CIRCUIT AMPACITY OF THE 5KW UNITS IS 13AMPS AND THE MAX |
| | OCP ID 20AMPS. THIS CAN NOT BE POSSIBLE AS THE LOAD OF |
| | 5KW AT 240V IS OVER 20AMPS. THIS IS BEFORE THE MINIMUM |
| | 125% WHICH IS REQUIRED BY CODE. |
| | PLEASE SEE THE UNIT WHICH SHOWS A 12.9 KW HEAT STRIP |
| | SHOWS MINIMUM CIRCUIT LOAD OF 20AMPS AND THE MAXIMUM |
| | OCP AT 40AMPS. THIS IS ALSO NOT POSSIBLE AS THE LOAD ON |
| | THIS UNIT BEFORE 125% IS SUBSTANTIALLY HIGHER THAN THE |
| | 40AMP BREAKER OR CIRCUIT. |
| | PLEASE SEE 424.3B, 240.4, 310.16 ETC. |
| | |
| | ** PLEASE SEE THE ARCHITECTURAL PLANS STATE AND SHOW A |
| | AHU #4, WHEREAS THE MECHANICAL PLANS SHOWS THE AHU#3 IN |
| | THE SAME LOCATION. |
| | |
| | 4) NOTE: PLEASE SEE THE MINIMUM PHOTO-METRIC LEVELS ON |
| | THE OUTSIDE STAIRS DO NOT MEET THE LIFE SAFETY CODE FOR |
| | COMPLIANCE. |
| | PLEASE SEE 7.8.1.3 AS THIS REQUIRES A *MINIMUM* OF |
| | 10FOOT CANDLES. THE PLANS SHOWS ABOUT HALF OF THE |
| | NEEDED FOR NORMAL LIGHTING LEVELS. |
| | |
| | 5) NOTE: PLEASE SEE A NOTICE TO FS 553.80(2)(B) IS NOW |
| | BEING GIVEN. THERE ARE REPEAT COMMENTS FOR CODE |
| | COMPLIANCE WHICH HAS BEEN MADE ON THE LAST TWO REVIEWS |
| | WHICH ARE BEING REPEATED ONCE AGAIN. THE INITIAL REVIEW |
| | DOES NOT APPLY AS PLANS WERE ONLY SUBMITTED FOR *PLAN |
| | REVIEW* AND WERE NOT SUBMITTED FOR PERMIT APPLICATION. |
| | |
| | PLEASE BE SURE ALL COMMENTS ARE ADDRESSED ON THE THIRD |
| | REVIEW UNDER PERMIT AND FORTH REVIEW FOR PROJECT. ONCE |
| | AGAIN AS STATED ON PREVIOUS REVIEWS IF THERE ARE |
| | QUESTIONS OR COMMENTS PLEASE CONTACT THIS REVIEWER. |
| | PLANS AND CALCULATIONS MAY BE RETAINED BY THIS OFFICE |
| | DUE TO THE REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | |
| | |
| | |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |