| Date |
Text |
| 2008-02-08 09:36:43 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | ****FROM PREVIOUS REVIEW: |
| | |
| | 1. OK |
| | 2. OK |
| | 3. OK |
| | |
| | 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE |
| | ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE |
| | 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC |
| | OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH |
| | WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES |
| | TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE |
| | TOILET AND LAV IN THE STALL/COMPARTMENT. |
| | ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT |
| | COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE |
| | W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF |
| | THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF |
| | THE W/C AS REQUIRED IN FIG 11-30E. |
| | |
| | 5. OK |
| | |
| | 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND |
| | SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH |
| | WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL |
| | OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS |
| | AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY. |
| | SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN |
| | THE STALL/COMPARTMENT. |
| | ****RESPONSE NOTED, BUT THE ACCESSIBLE STALL DOES NOT |
| | COMPLY WITH FIG 11-30E. THE CLEAR FLOOR SPACE FOR THE |
| | W/C IS NOT INDICATED ON THE FLOOR PLAN, AND THE SIDE OF |
| | THE LAV IS LESS THAN 5' OFF THE WALL ADJACENT TO THE OF |
| | THE W/C AS REQUIRED IN FIG 11-30E. |
| | |
| | 7. OK |
| | |
| | 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: |
| | ___W/C'S |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | ****NOT ADDRESSED |
| | ___URINAL |
| | A. 11-4.18.2 HEIGHT |
| | ****NOT ADDRESSED |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | ****NOT ADDRESSED |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | ****NOT ADDRESSED |
| | ___ FOR LAVS |
| | A. 11-4.19.5 FAUCETS |
| | ___SHOWERS |
| | A. 11-4.21.2 SIZE & CLEARANCES |
| | ****NOT ADDRESSED, SHOWS 3'-10-5/8" |
| | B. OK |
| | C. OK |
| | D. OK |
| | C. OK |
| | E. OK |
| | |
| | 9. OK |
| | 10. OK |
| | 11. OK |
| | 12. OK |
| | |
| | 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS |
| | REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL |
| | OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE |
| | RISER DIAGRAM. |
| | ****RESPONSE NOTED, BUT THE CIVIL PLANS HAVE NOT BEEN |
| | SUBMITTED. |
| | |
| | 14. OK |
| | |
| | 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT |
| | DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT |
| | INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3 |
| | INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V. |
| | PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO |
| | INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL |
| | WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL |
| | CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL |
| | SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION |
| | 13-103. |
| | ****NO RESPONSE, NOT ADDRESSED. (ALSO SEE COMMENT |
| | NUMBER ONE OF THE ELECTRICAL PLAN REVIEW). |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |