| Date |
Text |
| 2007-09-27 16:26:37 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FBC-2004 CHAPTER 11 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ALL SHEETS WITH DALIMA STUDIO TITLE BLOCK. THE FIRMS |
| | LICENSE NUMBER, (CERTIFICATE OF AUTHORIZATION), IS |
| | REQUIRED ON EACH SHEET. FAC 61G1-16.004(2) & FS |
| | 481.219, 481.2055. PLEASE INDICATE FIRM LICENSE NUMBER |
| | IN THE TITLE BLOCK ON EACH SHEET. |
| | |
| | 2. SHT A200. THE A-3 OCCUPANCY REQUIRES A DRINKING |
| | FOUNTAIN, BUT A BOTTLED WATER COOLER IS SHOWN. THIS IS |
| | NOT APPROVED. BOTTLED WATER DISPENSERS SHALL BE |
| | PERMITTED TO BE SUBSTITUTED FOR NOT MORE THAN 50% OF |
| | THE REQUIRED DRINKING FOUNTAINS. SINCE ONLY ONE |
| | DRINKING FOUNTAIN IS REQUIRED, THE BOTTLED WATER |
| | DISPENSER IS BEING SUBSTITUTED FOR 100% OF THE REQUIRED |
| | FIXTURES. TABLE 403.1 AND SECTION 410.1. PLEASE |
| | INDICATE THE LOCATION OF THE DRINKING FOUNTAIN. |
| | |
| | 3. SUBMIT A DETAIL FOR THE DRINKING FOUNTAIN SHOWING |
| | COMPLIANCE WITH SECTION 11-4.15 AND ALL SUBSECTIONS AS |
| | WELL AS SECTION 11-4.1.3(10)(A) PROVISIONS FOR THOSE |
| | WHO HAVE DIFFICULTY BENDING OR STOOPING. |
| | |
| | 4. SHT A700 WOMENS TOILET ROOM STALL SHALL BE |
| | ACCESSIBLE AND SHALL MEET THE REQUIREMENTS OF FIGURE |
| | 11-30E.--EACH WATER CLOSET UTILIZED BY THE PUBLIC |
| | OR EMPLOYEES SHALL OCCUPY A SEPARATE COMPARTMENT WITH |
| | WALLS OR PARTITIIONS AND A DOOR ENCLOSING THE FIXTURES |
| | TO ENSURE PRIVACY. SECTION 310.4. SHOW THE ACCESSIBLE |
| | TOILET AND LAV IN THE STALL/COMPARTMENT. |
| | |
| | 5. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV |
| | FOR THE W/C OUTSIDE THE ACCESSIBLE STALL. SECTION |
| | 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE |
| | THE ACCESSIBLE STALL. |
| | |
| | 6. SHT A700 MENS TOILET ROOM SHALL BE ACCESSIBLE AND |
| | SHALL MEET THE REQUIREMENTS OF FIGURE 11-30E.-- EACH |
| | WATER CLOSET UTILIZED BY THE PUBLIC OR EMPLOYEES SHALL |
| | OCCUPY A SEPARATE COMPARTMENT WITH WALLS OR PARTITIIONS |
| | AND A DOOR ENCLOSING THE FIXTURES TO ENSURE PRIVACY. |
| | SECTION 310.4. SHOW THE ACCESSIBLE TOILET AND LAV IN |
| | THE STALL/COMPARTMENT. |
| | |
| | 7. SHT A700 WOMENS TOILET ROOM WILL REQUIRE ANOTHER LAV |
| | FOR THE URINAL OUTSIDE THE ACCESSIBLE STALL. SECTION |
| | 405.3.2.. PLEASE SHOW THE LOCATION OF THE LAV OUTSIDE |
| | THE ACCESSIBLE STALL. |
| | |
| | 8. SHT A700 PLEASE SHOW COMPLIANCE FOR THE FOLLOWING: |
| | ___W/C'S |
| | A. 11-4.16.5 FLUSH CONTROLS |
| | ___URINAL |
| | A. 11-4.18.2 HEIGHT |
| | B. 11-4.18.3 CLEAR FLOOR SPACE |
| | C. 11-4.18.4 FLUSH CONTROLS |
| | ___ FOR LAVS |
| | A. 11-4.19.5 FAUCETS |
| | ___SHOWERS |
| | A. 11-4.21.2 SIZE & CLEARANCES |
| | B. 11-4.21.3 SEATS |
| | C. 11-4.21.4 GRAB BARS |
| | D. 11-4.21.5 CONTROLS |
| | C. 11-4.21.6 SHOWER UNITS |
| | E. 11-4.21.7 CURBS |
| | PLEASE SUBMIT DETAILS OR ELEVATIONS AND ADJUST DETAILS |
| | ALREADY SUBMITTED. SEE SECTION 11-4.23AND ALL |
| | SUBSECTIONS. |
| | |
| | 9. SHT P-1 DETAIL 1 THE SHOWER IN BATHROOM #2. PER |
| | TABLE 906.1 THE MAXIMUM DISTANCE FROM THE TRAP TO THE |
| | VENT FOR 2" IS 6FT. PER THE FLOOR PLAN, THIS SCALES OUT |
| | TO 8FT. PLEASE CHECK DISTANCE FROM TRAP TO VENT FOR THE |
| | SHOWER. |
| | |
| | 10. SHT P-1 DETAIL 1 APPLIANCE P-6 IS NOT INDICATED ON |
| | THE PLUMBING FIXTURE SCHEDULE FOUND ON SHT P-3. PLEASE |
| | INDICATE WHAT TYPE OF FIXTURE THIS IS. SECTION |
| | 106.1.1. |
| | |
| | 11. SHT P-1 DETAIL 1 BATHROOM 3 IS INDICATED AS CLOSET |
| | NO.3. PLEASE CLARIFY. (ALSO SEE OTHER SHEETS). SECTION |
| | 106.1.1. |
| | |
| | 12. SHT P-2 SANITARY RISER DIAGRAM. ITEM P-6. IF THE |
| | ITEM IS A WASH MACHINE, THEN 3" IS REQUIRED FOR THE |
| | BRANCH DRAIN AND STACK SECTION 406.3--ALSO A |
| | STANDPIPE IS REQUIRED FOR THE W/M PER SECTIONS 1002.1 & |
| | 802.4.--A CLEANOUT SHALL BE INSTALLED AT LEAST 4FT |
| | ABOVE THE FLOOR PER SECTION 708.9. PLEASE SHOW ON THE |
| | ISOMETRIC IF P-6 IS THE WASH MACHINE. |
| | |
| | 13. SHT P-2 WATER RISER DIAGRAM. AN RPZV BACKFLOW IS |
| | REQUIRED ON THE WATER SERVICE TO THE COMMERCIAL |
| | OCCUPANCY. SECTION 608.13.2. PLEASE INDICATE ON THE |
| | RISER DIAGRAM. |
| | |
| | 14. SHT P-3 PLEASE SUBMIT THE CALCULATIONS FOR THE |
| | EXPANSION TANK. PLEASE SUBMIT THE MANUF. SPECIFICATION |
| | SHEETS FOR THE EXPANSION TANK AND INDICATE THE MODEL |
| | NUMBER. SECTION 607.3.2. |
| | |
| | 15. THE ENERGY EFFICIENCY CODE SYSTEM COMPLIANCE REPORT |
| | DOES NOT REFLECT WHAT IS SHOWN ON SHT P-3. REPORT |
| | INDICATES NONE FOR THE WATER HEATER, BUT SHT P-3 |
| | INDICATES TYPICAL WATER HEATER 80 GAL, 4.5KW, 208V. |
| | PLEASE CORRELATE.--INPUT DATA REPORT ALSO SHOWS NO |
| | INFORMATION FOR THE WATER HEATER.--THE RESIDENTIAL |
| | WHOLE BUILDING PERFORMANCE METHOD A INDICATES A 50 GAL |
| | CAP. WATER HEATER WHICH DOES NOT RELFECT THE 80 GAL |
| | SHOWN ON SHT P-3. PLEASE CORRELATE INFORMATION. SECTION |
| | 13-103. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | REVIEW BY KEN STEVENS |
| | (561) 805-6721 |
| | FAX (561) 805-6731 |
| | E-MAIL [email protected] |