| Date |
Text |
| 2007-09-13 11:20:40 | |
| | ** DENIED ** |
| | |
| | *** IMPORTANT** |
| | PLANS HAVE ONLY BEEN SUBMITTED FOR PLAN REVIEW AND HAVE |
| | NOT BEEN SUBMITTED FOR PERMIT APPLICATION. |
| | PLEASE KNOW EVEN ONCE ALL CODE COMMENTS ARE ADDRESSED |
| | AND PERMIT HAS NOT BEEN APPLIED FOR BY A LICENSED |
| | CONTRACTOR, THE REVIEW WILL STILL REMAIN INA *F* |
| | STATUS UNTIL APPLICATION IS MADE. ALL LICENSING FOR |
| | CONTRACTORS, DESIGNERS WILL BE VERIFIED AT THAT TIME |
| | BEFORE PERMIT ISSUANCE. |
| | |
| | |
| | 1) NOTE: PLEASE CLARIFY EXISTING OCCUPANCY. |
| | |
| | 2) NOTE: PLEASE SEE CERTIFICATE OF AUTHORIZATION NUMBER |
| | SHOWN ON TITLE BLOCKS FOR ARCHITECTURAL FIRM IS NOT |
| | THAT AS LISTED WITH THE DEPARTMENT OF BUSINESS AND |
| | PROFESSIONAL REGULATION. PLEASE SEE THE ATTACHED PRINT |
| | OUT AS OF THIS REVIEW. |
| | PLEASE SEE FAC 61G1-16.004 AND FLORIDA STATUTES |
| | 481.219 |
| | |
| | 3) NOTE: PLEASE BE SURE THE RAISED/EMBOSSED SEAL ON THE |
| | ELECTRICAL SHEETS IS CLEAR AND VISIBLE WITH ALL |
| | INFORMATION ON SAID SEAL. SOMEARE VERY FAINT AND NOT |
| | EASILY READ. |
| | FS 471.025, FAC 61G15-23.001 |
| | |
| | 4) NOTE: PLEASE KNOW THAT ANY PERMIT APPLICATIONS WHICH |
| | ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES PROJECTS |
| | UNDER THE NEW CODES ADOPTED BY THE STATE. |
| | PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO |
| | THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70. |
| | PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY |
| | AFFECT DESIGNS FOR ALL TRADES. |
| | PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS |
| | REVIEWER AT A MINIMUM. |
| | 2004 FBC W/ 2006 REVISIONS |
| | 2005 NFPA-70 |
| | 2002 NFPA-72 |
| | 2003 NFPA-101 |
| | |
| | 5) NOTE: PLEASE SEE MECHANICAL REVIEW COMMENTS AS THE |
| | ADDITIONAL A/C BEING ADDED TO SPACE MAY REQUIRED ENERGY |
| | CALCULATIONS BY METHOD AS SPECIFIED IN 13-415.1.B, |
| | 13-415.1.C. |
| | PLEASE SEE THE LIGHTING ON THE INPUT DATA REPORT DO NOT |
| | CORRELATE WITH PLANS AND FIXTURE LEGEND. THE IDR ONLY |
| | INDICATES 3 FIXTURES TOTAL? |
| | PLEASE ALSO SEE METHOD A BEING SUBMITTED. |
| | PLEASE KNOW THAT LIGHTING PERFORMANCE CALCULATIONS ARE |
| | STILL REQUIRED PER 13-415.2. PLEASE SEE TABLES |
| | 415.2.C.1, 415.2.B.1. |
| | PLEASE BE SURE TO COORDINATE ALL OF THESE ITEMS. |
| | FBC 106.1.2, 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE INDICATE THE AIC RATINGS FOR NEW MAINS |
| | AND SERVICE EQUIPMENT AS SHOWN ON RISER. |
| | 110.9. SOME ARE SHOWN BUT NOT ALL. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 7) NOTE: PLEASE SEE THE RISER IS SHOWING *EQUIPMENT |
| | GROUNDING CONDUCTORS* AHEAD OF MAINS WHICH IS NOT |
| | PERMITTED. AS THE NEUTRAL/GROUNDED CONDUCTOR IS BONED |
| | AT THE FIRST MEANS OF DISCONNECT, IF AN *EQUIPMENT |
| | GROUNDING CONDUCTOR * WAS INSTALLED AHEAD OF MAINS, |
| | THIS WOULD CREATE OBJECTIONABLE CURRENTS PER 250.6, |
| | 250.24 |
| | PLEASE REMOVE. |
| | |
| | 8) NOTE: PLEASE SEE 310.16, 110.14, 240.4 AS THE 1/0 |
| | CONDUCTORS ARE NOT RATED FOR THE 175AMP BREAKER/OVER |
| | CURRENT PROTECTION TO PANEL *B*. |
| | |
| | 9) NOTE: PLEASE SEE LS 200 WHICH MENTIONS THE EMERGENCY |
| | FIXTURES ON AN EMERGENCY CIRCUIT, YET THERE IS NO |
| | GENERATOR BACK UP ON PLANS? |
| | PLEASE VERIFY AS THE ELECTRICAL PLANS INDICATES THE |
| | CIRCUITING CORRECTLY PER 700.12F. |
| | |
| | 10) NOTE: PLEASE CORRELATE PLANS WITH RISER FOR ALL |
| | FEEDERS. PLEASE SEE THE RISER SHOWS SERVICE ENTRANCE |
| | CONDUCTORS AND FEEDERS FOR THREE PHASE TO PANEL *A* YET |
| | PANEL *A* IS SHOWN AS SINGLE PAHSE. PLEASE CORRELATE |
| | AND ADJUST. |
| | FBC 106.1.2 FOR COORDINATION. |
| | |
| | 11) NOTE: PLEASE CORRELATE FEEDERS ON RISER AND PANEL |
| | SCHEDULE FOR PANEL *B* AS PANEL INDICATES 2/0 AND THE |
| | RISER SHOWS 1/0. PLEASE SEE PREVIOUS NOTE ABOVE #7 AS |
| | THE 1/0 CONDUCTORS ARE NOT RATED FOR THE 175AMPS. |
| | PLEASE CORRELATE AND ADJUST. |
| | FBC 106.1.2, 106.3.5.1.2, ETC |
| | |
| | 12) NOTE: PLEASE SEE THE RISER WHICH INDICATES BUILDING |
| | STEEL AS PART OF THE GROUNDING ELECTRODE SYSTEM. THIS |
| | IS BEING ASSUMED THIS IS ACTUALLY *FOOTER STEEL*? IN |
| | EITHER CASE PLEASE KNOW AS THIS IS AN EXISTING BUILDING |
| | THE FOOTER STEEL WOULD NOT REQUIRE AN ATTACHMENT AS |
| | THIS MAY CREATE AN ADVERSE AFFECT ON THE STRUCTURAL |
| | INTEGRITY OF THE FOUNDATION. |
| | (IF SHOWN ON RISER, THEN THIS WOULD BE REQUIRED AS THIS |
| | IS BEING SPECIFIED.) |
| | PLEASE SEE MISSING GAS LINE BOND AS REQUIRED. 250.50, |
| | 250.104. |
| | |
| | 13) NOTE: PLEASE SEE NEC 422.13 AS THE WATER HEATER IS |
| | REQUIRED TO BE FIGURED AT 125% FOR LOAD. PLEASE KNOW |
| | THIS WAS A CHANGE IN THE 2005 NEC. |
| | 230.42, 215.3, 422.13 ETC |
| | |
| | 14) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR THE MINIMUM |
| | LIGHTING LEVELS UNDER NORMAL AND EMERGENCY CONDITIONS |
| | PER NFPA-101 7.8.1.3, 7.9.2.2 FOR STAIRS/DESIGNATED |
| | EGRESS PATHS. |
| | FLORIDA ADMINISTRATIVE CODE 61G15-33.004 |
| | |
| | 15) NOTE: PLEASE INDICATE THE SIZE/AMPERAGE OF METER |
| | CANS. |
| | PLEASE VERIFY RISER AS SHOWN WITH AN ADDITIONAL GUTTER |
| | ON THE SECONDARY SIDE OF THE METER. |
| | FBC106.1.2 |
| | |
| | 16) NOTE: PLEASE SEE PANEL SCHEDULES NEED TO BE |
| | SPECIFIC TO THE ROOMS AND AREAS IN WHICH THEY FEED. |
| | PLEASE SEE THE FOLLOWING TEXT WHICH IS TAKEN DIRECTLY |
| | FROM THE NEC. |
| | *SECTION 408.4 WAS REVISED FOR THE 2005 CODE TO REQUIRE |
| | THAT THE IDENTIFICATION FOR EVERY CIRCUIT SUPPLIED BY A |
| | PANEL-BOARD OR SWITCHBOARD BE LEGIBLE AND CLEARLY STATE |
| | THE SPECIFIC PURPOSE FOR WHICH THE CIRCUIT IS USED. |
| | CIRCUITS USED FOR THE SAME PURPOSE MUST BE IDENTIFIED |
| | AS TO THEIR LOCATION. FOR EXAMPLE, SMALL APPLIANCE |
| | BRANCH CIRCUITS CAN SUPPLY OUTLETS IN THE KITCHEN, |
| | DINING ROOM, AND KITCHEN COUNTERTOPS. IDENTIFYING THE |
| | CIRCUITS AS SMALL APPLIANCE BRANCH CIRCUITS IS NOT |
| | ACCEPTABLE; INSTEAD, THEY SHOULD BE IDENTIFIED AS |
| | ``KITCHEN WALL RECEPTACLES,'' ``DINING ROOM FLOOR |
| | RECEPTACLE,'' OR ``KITCHEN COUNTERTOP RECEPTACLES LEFT |
| | OF SINK.'' CIRCUIT DIRECTORIES CONTAINING MULTIPLE |
| | ENTRIES WITH ONLY ``LIGHTS'' OR ``OUTLETS'' DO NOT |
| | PROVIDE THE SUFFICIENT DETAIL REQUIRED BY THIS |
| | SECTION.* |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.3.5.4 |
| | |
| | 17) NOTE: PLEASE VERIFY THE SMOKE DETECTION DEVICES, |
| | TYPES AND DESIGNATIONS ON PLANS. |
| | PLEASE SEE NFPA-72 AS SMOKE DETECTORS ARE ONLY DEVICES |
| | WHICH DETECT AND DO NOT SOUND AN ALARM AND SMOKE ALARMS |
| | DETECT AND SOUND AN ALARM. |
| | IF TWO DIFFERENT TYPES OF DEVICES ARE BEING USED AS IT |
| | SEEMS, PLEASE ADJUST DESIGNATIONS. |
| | |
| | 18) NOTE: PLEASE SEE 210.12 AS ALL *OUTLETS* IN |
| | SLEEPING ROOMS REQUIRE ARC FAULT PROTECTION. |
| | PLEASE KNOW THIS INCLUDES RECEPTACLES, LIGHTS, SMOKE |
| | ALARMS, FANS ETC. |
| | |
| | 19) NOTE: PLEASE SEE MISSING CIRCUITS/LIGHTS/GFI PER |
| | 620.24. |
| | PLEASE ALSO SEE HANDBOOK REFERENCES THE ANSI/ASME 2004 |
| | ELEVATOR SAFETY CODE FOR MINIMUM LIGHTING LEVELS IN PIT |
| | AREA. (5FT CANDLES) PLEASE ALSO SEE ANY MINIMUM |
| | REQUIREMENTS FROM THE STATE OF FLORIDA AND STATE |
| | ELEVATOR CODE WHICH MAY BE MORE RESTRICTIVE. |
| | |
| | 20) NOTE: PLEASE SPECIFY ALL LIGHTING FOR |
| | CLOSETS/LOCKERS AS THEY ARE REQUIRED TO MEET 410.8. |
| | PLEASE KNOW THIS IS ALSO REQUIRED OF THE DWELLING UNIT |
| | CLOSET. *(PLANS NOTE LIGHT FIXTURES TO BE OWNER CHOSEN, |
| | HOWEVER NEED TO MEET MINIMUM LIFE SAFETY CODE AT THIS |
| | TIME.) |
| | |
| | 21) NOTE: PLEASE SEE ANY COMMENTS FROM OTHER TRADES |
| | WHICH MAY AFFECT THE ELECTRICAL PLANS AND/OR DESIGN FOR |
| | BUILDING. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| | PICKED UP FOR CORRECTIONS, PLEASE BE |
| | SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| | SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| | AND STAMPING. DO NOT LEAVE ANY |
| | OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE |
| | OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| | FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND |
| | AVOID ANY DELAYS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |