| Date |
Text |
| 2007-08-28 07:37:11 | |
| | |
| | ** DENIED ** |
| | |
| | 1) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, 13-101 AS A |
| | NEW AUTOMATED DEVICE OF SOME KIND WILL BE REQUIRED FOR |
| | SWITCH LOCATIONS. |
| | PLEASE PROVIDE AND SHOW THE LOCATION OF THE NEW DEVICE |
| | OR DEVICES DEPENDING ON THE TYPE OF DEVICE AND COVERAGE |
| | FOR CONTROLS. |
| | PLEASE PROVIDE THE MAXIMUM TIME(S) FOR DEVICE(S). |
| | |
| | 2) NOTE: PLEASE PROVIDE INFORMATION FOR CIRCUITING OF |
| | WHAT IS BEING CALLED EXISTING EXIT AND EMERGENCY LIGHTS |
| | PER 700.12F OF THE 2005 NEC> ( ONE MISSING CONNECTION |
| | OF CIRCUIT) |
| | |
| | 3) NOTE: PLEASE SEE THE OPEN OFFICE AREA WHERE THE |
| | EMERGENCY LIGHT FIXTURE IS BEING RELOCATED DOES NOT |
| | SEEM TO BE PLACED IN THE OPEN OFFICE AREA. |
| | PLEASE SEE THE MINIMUM FT CANDLES FOR EGRESS PER LS 101 |
| | 7.8 AND 7.9 |
| | PLEASE MOVE THE FIXTURE AS SHOWN OR PROVIDE AN |
| | ADDITIONAL FIXTURE. |
| | FAC 61G15-33.004 |
| | |
| | 4) NOTE: PLEASE PROVIDE THE MAXIMUM LIGHTING POWER |
| | DENSITIES PER 13-415.2 |
| | |
| | 5) NOTE: PLEASE PROVIDE A PANEL SCHEDULE FOR NEW AND/OR |
| | EXISTING CIRCUITS. |
| | 408.4. |
| | FBC 106.3.5.1.2, 106.1.2 |
| | |
| | 6) NOTE: PLEASE STATE THE FOLLOWING CODES ON PLANS. |
| | 2005 NFPA-70 (NEC) |
| | 2003 NFPA-101 |
| | 2002 NFPA-72 |
| | |
| | ** THE SCOPE OF WORK IN MINOR IN NATURE AND THERE ARE |
| | ONLY A FEW ITEMS NEEDED ON PLANS. |
| | |
| | PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |