| 2007-09-06 15:06:47 | ----------------DENIED--------------- |
| | |
| | FBC 2004 W/ 2005 AND 2006 REVISIONS. |
| | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH |
| | |
| | 1. PLANS SHALL BE OF SUFFICIENT CLARITY TO INDICATE THE |
| | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED AND |
| | SHOW IN DETAIL THAT IT WILL CONFORM TO THE PROVISIONS |
| | OF THIS CODE, RELEVANT LAWS, ORDINANCES, RULES AND |
| | REGULATIONS, AS DETERMINED BY THE BUILDING OFFICIAL. |
| | FBC 106.1.1. |
| | |
| | 2. THE WORK PROPOSED A LOUNGE AREA TO BE CONVERTED TO A |
| | PUBLIC RESTROOM. THIS CONSTITUTES AN INTERIOR REMODEL |
| | AND AS SUCH, AN INTERIOR REMODEL PERMIT IS REQUIRED. IN |
| | CONJUNCTION, SEPARATE SUB PERMITS ARE REQUIRED FOR ALL |
| | PLUMBING, ELECTRICAL AND MECHANICAL WORK AS REQUIRED TO |
| | CONVERT THIS SPACE IN A CODE COMPLIANT MANNER. |
| | |
| | 3. THE PLANS WHICH WERE SUBMITTED CONTAIN AN |
| | ARCHITECT'S TITLE BLOCK. THIS WOULD MAKE OBS AND |
| | ASSOCIATES, AIA THE DESIGNERS OF RECORD FOR THIS |
| | PROJECT. AS SUCH, HE OR SHE SHALL AFFIX HIS OR HER |
| | OFFICIAL SEAL, SIGNATURE AND DATE TO SAID DRAWINGS, |
| | SPECIFICATIONS AND ACCOMPANYING DATA, AS REQUIRED BY |
| | FLORIDA STATUTE. FBC 106.1 |
| | |
| | 4. PUBLIC TOILET ROOMS REQUIRE MECHANICAL VENTILATION |
| | AT A RATE OF 50 CFM PER WATER CLOSET OR URINAL IN |
| | ACCORDANCE WITH FBC,M TABLE 403.3. |
| | |
| | 5. PROVISIONS SHALL BE MADE TO PROVIDE THE MINIMUM RATE |
| | OF VENTILATION WHENEVER THE SPACE IS OCCUPIED IN |
| | ACCORDANCE WITH FBC,M 401.2 |
| | |
| | 6. ALL AIR BEING SUPPLIED TO SUCH SPACES SHALL BE |
| | EXHAUSTED, INCLUDING ANY AIR SUPPLIED IN EXCESS OF THAT |
| | REQUIRED PER TABLE 403.3, AND IS PROHIBITED FROM BEING |
| | RECIRCULATED IN ACCORDANCE WITH FBC,M 403.2.1(3). |
| | |
| | 7. PROVIDE EQUIPMENT SCHEDULE SHOWING EXHAUST FAN BEING |
| | USED, CFM AND ELECTRICAL RATINS. ALSO SHOW SIZE AND |
| | LOCATION OF DUCTWORK PER FBC 106.3.5.1.4. |
| | |
| | 8. SHOW MECHANICAL EXHAUST TERMINATION LOCATION WHICH |
| | IS IN COMPLIANCE WITH FBC,M 401.5 |
| | |
| | 9. SHOW EXHAUST OUTDOOR OPENING PROTECTION IN |
| | ACCORDANCE WITH FBC,M 401.6 |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: |