Plan Review Notes
Plan Review Notes For Permit 07080394
Permit Number 07080394
Review Stop E
Sequence Number 2
Notes
Date Text
2007-09-19 07:54:56 
  
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 COMMENT FROM PREVIOUS REVIEW DONE ON 8/28/07:
  
 2}PER CHAPTER 13 FBC, SUBCHAPTER 13-400.0.C.4,
 PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER
 13-415.2. AND CERTIFICATION PER 13-103.1.2.
 THIS COMMENT MUST BE ADDRESSED PER THE FOLLOWING:
  
 13-400.0.C.4 RENOVATED BUILDINGS.
 RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION
 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR
 COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE
 ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR
 THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT
 MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW
 HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING
 SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE
 MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE
 SYSTEM(S) BEING CHANGED.
  
 13-400.3.ABC.2 CODE COMPLIANCE CERTIFICATION.
 THE BUILDING'S OWNER, THE OWNER'S ARCHITECT, OR OTHER
 AUTHORIZED AGENT LEGALLY DESIGNATED BY THE OWNER SHALL
 CERTIFY TO THE BUILDING OFFICIAL THAT THE BUILDING IS
 IN COMPLIANCE WITH THE REQUIREMENTS OF CHAPTER 13 OF
 THIS CODE PRIOR TO RECEIVING THE PERMIT TO BEGIN
 CONSTRUCTION OR RENOVATION.
  
 THE RESPONSE THAT THE "G.C. WILL PROVIDE"GIVEN AUGUST
 29TH, IS ACCEPTABLE, BUT PER 13-400.3ABC.2 IT MUST BE
 SUBMITTED WITH THE PLANS TO VERIFY COMPLIANCE AT THE
 REVIEW LEVEL. ALSO IT HAS BEEN DETERMINED BY THIS
 OFFICE THAT THE INTENT OF THIS ARTICLE DOES NOT MANDATE
 A "CERTIFICATE" BUT"THE CERTIFIED FLA/COM
 CALCULATION PRINTOUT OR FORM 400C SHALL BE A PART OF
 THE PLANS AND SPECIFICATIONS SUBMITTED FOR PERMITTING."
 THEREFORE FORM 400C COULD BE USED INSTEAD OF METHOD "B"
 WHICH REQUIRES A FLA/COM CALCULATION PRINTOUT. BUT
 DENSITY AND LIGHTING CONTROLS MUST BE SUBMITTED FOR
 REVIEW, AND THE FIXTURE SCHEDULE MUST AGREE.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]