Plan Review Notes
Plan Review Notes For Permit 07080394
Permit Number 07080394
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-05 16:03:45DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. SEE BUILDING PLAN REVIEW COMMENTS 3# AND #4 AND
 COMPLY ON THE RESUBMITTAL.
  
 2. PER FBC-2004 WITH 2006 REVISIONS PLUMBING, TABLE
 403.1(2) A DRINKING FOUNTAIN IS REQUIRED. PLEASE
 CLEARLY INDICATE AN EXISTING ONE IN THE COMMON AREA OR
 PROVIDE ONE IN THE PROPOSED RENOVATION. IF ONE IS
 PROVIDED IN THE PROPOSED RENOVATION A SANITARY
 ISOMETRIC RISER DIAGRAM AND A WATER ISOMETRIC RISER
 DIAGRAM ARE ALSO REQURED PER FBC-2004 CHAPTER 1 SECTION
 106.3.5.1.3, AND MUST BE ADA COMPLIANT PER FBC-2004
 CHAPTER 11 FLORIDA ACCESSIBILITY CODE SECTIONS 11-4.15
 THRU 11-4.15.5 (ELEVATION DETAIL REQUIRED) AND
 11-4.1.3(10) FOR INDIVIDUALS WHO HAVE DIFFICULTY
 BENDING AND STOOPING.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL= [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved