| 2007-08-28 16:17:37 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS | | | DESIGNED UNDER, 2005 NEC,ADD TO NOTES FOR CLARITY IN | | | THE FIELD AND RECORD RETENTION. SEE "CODES" SHEET "T". | | | | | | 2}PER CHAPTER 13 FBC, SUBCHAPTER 13-400.0.C.4, | | | PROVIDE PERFORMANCE CALCULATIONS FOR REVIEW PER | | | 13-415.2. AND CERTIFICATION PER 13-103.1.2. | | | | | | 3} SHEET E2 PANEL 9CL HAS A 200 AMP CIRCUIT BREAKER. | | | TABLE 450.3(B) SHOWS THAT THE SECONDARY OF THE 45 KVA | | | TRANSFORMER MUST HAVE OCP AT NOT MORE THAN 125%, OR THE | | | NEXT HIGHER STANDARD BREAKER, 175 AMP IN THIS CASE. | | | PLEASE FIELD VERIFY, EVEN IF THE FEED IS EXISTING IT | | | MUST BE CORRECTED. ALSO INDICATE THE CONDUCTOR SIZES. | | | | | | PLEASE REMOVE OLD SHEETS, INSERT NEW | | | ONES, SUBMIT OLD SHEETS TO EXPEDITE | | | REVIEW AND SUBMIT WRITTEN RESPONSE TO | | | THE COMMENTS MADE IN THIS REVIEW. | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | [email protected] |
|