| 2007-10-23 08:54:40 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.SEE OPENING 4.A 70" OPENING, 3" EDGE DISTANCE, | | | SHOULD HAVE A SPAN OF 73" (BLADE LENGTH), REQUIRING USE | | | OF THE 9' SPAN CHART RATHER THAN THE 6' SPAN CHART. | | | CHECK ALL OPENINGS. | | | | | | 2.C2, 47.2PSF, 15' SPAN, REQUIRES 15" ANCHOR SPACING. | | | OPENING 1 SPECIFIES TOP CONNECTION ANCHOR SPACING WILL | | | BE 16".PLEASE REVISE AND CHECK ALL OPENINGS. | | | |
|