| 2007-08-15 10:11:28 | *** PROVISO *** | | | 1) INSPECTOR TO VERIFY HOOD IS AN EXISTING TYPE 1 | | | GREASE HOOD. TYPE 1 HOODS SHALL BE CONSTRUCTED OF STEEL | | | NOT LESS THAN 0.043 INCH (1.09 MM) (NO. 18 MSG) IN | | | THICKNESS, OR STAINLESS STEEL NOT LESS THAN 0.037 INCH | | | (0.94 MM) (NO. 20 MSG) IN THICKNESS, SEE 2004 FBC/M | | | 507.4. | | | 2) GREASE DUCTS SERVING TYPE 1 HOODS SHALL BE | | | CONSTRUCTED OF STEEL NOT LESS THAN 0.055 INCH (1.4 MM) | | | (NO. 16 GAGE) IN THICKNESS OR STAINLESS STEEL NOT LESS | | | THAN 0.044 INCH (1.1 MM) (NO. 18 GAGE) IN THICKNESS, | | | SEE 2004 FBC/M 506.3.1.1. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|