| 2007-08-14 17:07:44 | PROJECT: 1920 PALM BEACH LAKES BLVD. | | | | | | PROJECT DETAIL: INSTALL MARBLE FLOORING | | | | | | PLAN REVIEW: 2004 FL. EXISTING BUILDING CODE/2006 | | | REVISIONS | | | 2004 FLORIDA BUILDING CODE/2006 REVISIONS | | | | | | STATUS: DENIED | | | | | | | | | COMMENTS: | | | | | | 1) REQUIREA SIGNED/SEALED STRUCTURAL ENGINEERING | | | LETTER APPROVING THE ADDITIONAL MARBLE DEADLOAD IMPOSED | | | ON THE | | | EXISTING 2ND FLOOR SLAB. | | | | | | 2) DOOR THRESHOLDS SHALL COMPLY WITH THE FOLLOWING: | | | | | | SECTION 506 | | | | | | ACCESSIBILITY | | | 506.1 | | | ACCESSIBILITY SHALL BE IN ACCORDANCE WITH CHAPTER 11 OF | | | THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1008.1.6 THRESHOLDS. | | | THRESHOLDS AT DOORWAYS SHALL NOT EXCEED 0.75 INCH (19.1 | | | MM) IN HEIGHT FOR SLIDING DOORS SERVING DWELLING UNITS | | | OR 0.5 INCH (12.7 MM) FOR OTHER DOORS. RAISED | | | THRESHOLDS AND FLOOR LEVEL CHANGES GREATER THAN 0.25 | | | INCH (6.4 MM) AT DOORWAYS SHALL BE BEVELED WITH A SLOPE | | | NOT GREATER THAN ONE UNIT VERTICAL IN TWO UNITS | | | HORIZONTAL (50-PERCENT SLOPE). | | | | | | | | | PLAN REVIEW: KEN CONRAD | | | PHONE: 561.805.6666 | | | E-MAIL; [email protected] |
|