Plan Review Notes
Plan Review Notes For Permit 07080333
Permit Number 07080333
Review Stop B
Sequence Number 2
Notes
Date Text
2007-08-29 20:19:00THE FOLLOWING REVIEW IS BASED ON THE PREVIOUSLY
 SUBMITTED PLANS NOT THE DO KIM P.E. PLANS SUBMITTED ON
 8/28/07.A SEPARATE REVIEW IS TO FOLLOW.
  
 FBC = FLORIDA BUILDING CODE 2004 (WITH 2007
 AMENDMENTS)
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 1) FBC 1603.1.4WIND DESIGN DATA.THE
 PLANS SHALL STATE THE BASIC WIND SPEED,
 WIND IMPORTANCE FACTOR, WIND EXPOSURE
 CATEGORY, INTERNAL PRESSURE COEFFICIENT,
 AND EXTERIOR COMPONENT AND CLADDING
 DESIGN WIND PRESSURES.ADD THIS
 INFORMATION TO THE PLANS.
  
 2) FBC 2002.4.1LOADS.THE PLANS MAKE REFERENCE TO
 SENATE BILL 404.SENATE BILL 404 STATES THAT SITE
 SPECIFIC ENGINEERING IS NOT REQUIRED FOR SCREEN
 ENCLOSURES.IT ALSO STATES THAT A"MASTER DESIGN
 MANUAL" CAN BE USED IF IT IS PREPARED BY A LICENSED
 ENGINEER, STATES THE DESIGN LIMITATIONS, STATES THE
 TRAINING REQUIRED TO BE A QUALIFIED USER, AND
 IDENTIFIES THE NAME OF THE ENGINEER WHO DID PEER REVIEW
 OF THE "MASTER DESIGN MANUAL".NO SUCH "MASTER DESIGN
 MANUAL" IS REFERENCED ON THE PLANS, SO WITH THE
 EXCEPTION OF THE SITE-SPECIFIC LAYOUT THE PLANS MUST BE
 PREPARED BY A LICENSED ENGINEER.THE STRUCTURAL
 MEMBERS SHALL BE DESIGNED IN ACCORDANCE WITH
 ESTABLISHED ENGINEERING PRACTICES.NO ENGINEERED PLANS
 WERE SUBMITTED FOR THE DESIGN OF THE STRUCTURAL
 MEMBERS.NON-ENGINEERS WHO ARE REGISTERED USERS OF AAF
 GUIDE TO ALUMINUM CONSTRUCTION IN HIGH WIND AREAS CAN
 SUBMIT DESIGNS BASED ON THAT GUIDE, BUT SCREEN
 PROFESSIONALS INC. IS NOT LISTED AS A REGISTERED USER.
 SUBMIT PLANS FROM A LICENSED ENGINEER, OR MAKE
 REFERENCE TO AN "MASTER DESIGN MANUAL" THAT MEETS THE
 ABOVE CRITERIA.
  
 3) FBC 2002.4TRAC SELF MATING BEAM.SHEET 2 OF THE
 SUBMITTED PRODUCT APROVAL FL 7350.1 STATES THAT "SITE
 SPECIFIC ENGINEERING MUST ACCOMPANY THIS PRODUCT
 APPROVAL FOR EACH STRUCTURE INSTALLED".IT ALSO STATES
 JUST TWO SIZES, 2"X 5" AND 2"X 7", AND GIVES SPAN
 LIMITATIONS OF 25'-0" AND 40'-0" RESPECTIVELY.NO SITE
 SPECIFIC ENGINEERING WAS SUBMITTED.ALSO, THE PLANS
 SHOW A 2"X 8" TRAC BEAM SPANNING 44'-6" BUT THAT TRAC
 BEAM SIZE IS NOT COVERED BY THE SUBMITTED PRODUCT
 APPROVAL AND THE SPAN EXCEEDS THE STATED LIMITATION OF
 40'-0".SUBMIT ENGINEERING TO JUSTIFY THE PROPSED
 STRUCTURAL MEMBER SIZES.
  
 4) FBC 2002.4CARRIER BEAM ACROSS RECESS IN THE HOST
 STRUCTURE.THE 2"X 6" CARRIER BEAM IS SHOWN TO BE
 SUPPORTING ONE END OF A 25'-11" LONG 2"X 7" TRAC BEAM
 VIA A SUPER GUTTER.SUBMIT ENGINEERING FOR THE DESIGN
 OF THE CARRIER BEAM SUPPORTING THIS POINT LOAD, AND FOR
 THE CARRIER BEAM SUPPORT.
  
 5) FBC 2002.3MEMBER WALL THICKNESS.THE THICKNESS OF
 EXTRUDED ALUMINUM MEMBERS SHALL BE NOT LESS THAN 0.04
 INCH.THE THICKNESS OF THE 2"X 7" TRAC BEAM IS GIVEN
 ON THE PRODUCT APPROVAL, BUT THE THICKNESS OF THE
 PURLINS AND BRACES IS NOT STATED ON THE PLANS.STATE
 THICKNESS FOR ALL EXTRUDED ALUMINUM MEMBERS.
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]
  
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved