2007-08-14 12:44:01 
  
  
  
  
 DENIED/INCOMPLETE INFORMATION
  
 1} THERE ARE THREE STRUCTURES ON THE PROPERTY OF
 APPLICATION. PROVIDE A SITE PLAN INDICATING THE
 LOCATION OF THIS SERVICE.
  
 2} PROVIDE THE AIC RATING OF THE EQUIPMENT BEING
 INSTALLED. OBTAIN THE AVAILABLE FAULT CURRENT
 INFORMATION AT THE TRANSFORMER FROM FPL.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]