| 2007-10-09 09:51:59 | DENIED 2ND TIME | | | REFERENCE: | | | ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS. | | | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION | | | REQUIREMENTS. | | | ** FBC-2004 CHAPTER 1, THE CITY OF | | | WEST PALM BEACH AMENDMENTS. | | | ** FLORIDA ADMINISTRATIVE CODE. | | | ** FLORIDA STATUTES. | | | | | | **THE RESUBMITTED PLANS WITH THE REQUESTED MP GAS | | | REGULATOR INFORMATION NEEDS THE FOLLOWING CORRECTIONS | | | PER THE SUBMITTED MANUFACTURER'S SPECIFICATION | | | REGULATOR INFORMATION: | | | | | | 1. THE MP REGULATOR MAXITROL325-7L HAS A MAXIMUM | | | INDIVIDUAL LOAD OF 900,000 BTU'S THE PROPOSED GENERATOR | | | HAS A 960,000 LOAD CAPACITY. THE INDICATED MAXITROL MP | | | REGULATOR 325-7L ON THE RESUBMITTED PLANS IS TO SMALL | | | FOR THE PROPOSED 960,000 GENERATOR. PLEASE RESUBMIT | | | WITH THE PROPER SIZED MP REGULATOR. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|