Plan Review Notes
Plan Review Notes For Permit 07080321
Permit Number 07080321
Review Stop G
Sequence Number 2
Notes
Date Text
2007-10-09 09:51:59DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, FUEL GAS.
 ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION
 REQUIREMENTS.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE.
 ** FLORIDA STATUTES.
  
 **THE RESUBMITTED PLANS WITH THE REQUESTED MP GAS
 REGULATOR INFORMATION NEEDS THE FOLLOWING CORRECTIONS
 PER THE SUBMITTED MANUFACTURER'S SPECIFICATION
 REGULATOR INFORMATION:
  
 1. THE MP REGULATOR MAXITROL325-7L HAS A MAXIMUM
 INDIVIDUAL LOAD OF 900,000 BTU'S THE PROPOSED GENERATOR
 HAS A 960,000 LOAD CAPACITY. THE INDICATED MAXITROL MP
 REGULATOR 325-7L ON THE RESUBMITTED PLANS IS TO SMALL
 FOR THE PROPOSED 960,000 GENERATOR. PLEASE RESUBMIT
 WITH THE PROPER SIZED MP REGULATOR.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER