| 2007-08-20 10:19:41 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72, 2002, |
| | 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT |
| | WITH THE FOLLOWING: |
| | |
| | THERE IAS NO BUILDING RECORDED AT THIS ADDRESS OR FOR |
| | THE PCN NUMBER ON THE APPLICATION |
| | |
| | 1} PLEASE INDICATE THE CODE CYCLES THIS PROJECT WAS |
| | DESIGNED UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES |
| | FOR CLARITY IN THE FIELD. |
| | |
| | 2} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN, |
| | METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT |
| | COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED. |
| | INDICATE IF SERVICE IS NEW OR EXISTING. |
| | |
| | 3} PER 110.9 AND 110.10: OBTAIN THE |
| | AVAILABLE FAULT CURRENT AT THE UTILITY |
| | AND CALCULATE THE SAME AT THE EQUIPMENT. |
| | INDICATE THE AIC RATING FOR THE |
| | EQUIPMENT IS EQUAL TO OR GREATER THAN |
| | THE AVAILABLE FAULT. |
| | |
| | 4} PLEASE PROVIDE A PANEL SCHEDULE SO THAT |
| | BRANCH/FEEDER CIRCUIT CONDUCTOR AND OVER CURRENT |
| | PROTECTION COMPLIANCE MAY BE REVIEWED PER 106.3.5.4 FBC |
| | AS AMENDED. |
| | |
| | 5}SEE THE DEFINITION OF "SMOKE DETECTORS" 11.8.2.1 |
| | NFPA-72, CLARIFY IF USING DETECTORS OR ALARMS, TO AVOID |
| | CONFUSION IN THE FIELD. IF USING DETECTORS INDICATE THE |
| | LOCATIONS OF THE SOUNDING DEVICES. |
| | |
| | NOTE: THE JURISDICTION ON THE COVER SHEET IS |
| | INCORRECT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |