| Date |
Text |
| 2007-08-16 16:27:48 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. PLEASE CORRELATE THE GAS ISOMETRIC WITH THE FLOOR |
| | PLAN PER FBC-2004 CHAPTER 1 SECTION 106.1.1. THE GAS |
| | ISOMETRIC DOES NOT REFLECT THE FLOOR PLAN IN THE |
| | FOLLOWING AREAS. PLEASE SEE THE RED LINE CORRECTIONS |
| | MADE BY THIS PLAN REVIEWER REFLECTING THIS. |
| | |
| | A} SHEET 06: DRYER IS LOCATED IN THE WRONG PLACE ON |
| | THE ISOMETRIC. |
| | |
| | B} SHEET 06: THE GAS PIPE DROP TO THE COOK TOP IS |
| | MISSING FROM THE FLOOR PLAN DRAWING. |
| | |
| | 2. PLEASE CLEARLY INDICATE THE GAS TYPE ON SHEET 06 AS |
| | BEING NATURALGAS ON THE RESUBMITTAL. |
| | |
| | 3. PLEASE SUBMIT MANUFACTURER SPECIFICATIONS ON THE MP |
| | REGULATORS BEING USED WITH THE FOLLOWING INFORMATION. |
| | |
| | A} MAKE. |
| | |
| | B} MODEL NUMBER. |
| | |
| | C} LOAD CAPACITY. |
| | |
| | D} A LISTING FROM A NATIONALLY RECOGNIZED TESTING |
| | AGENCY. |
| | |
| | 4. PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF EACH MP REGULATOR. PLEASE CLEARLY |
| | INDICATE THESE SHUT OFF VALVES ON THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL= [email protected] |