| Plan Review Notes For Permit 07080301 |
| Permit Number |
07080301 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-08-29 17:21:42 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.)THE SCOPE OF WORK CHANGED SINCE FIRST REVIEW | | | (ADDED TO APPLICATION, A SHEET WITH "SCOPE OF WORK" AT | | | THE TOP WAS INCLUDED).THIS IS ACCEPTABLE BUT HAS | | | RESULTED IN NEW COMMENTS.PAPERWORK FOR ORIGINAL SCOPE | | | OF WORK APPEARS CODE COMPLIANT (OTHER THAN PROVIDING | | | TWO COMPLETE SETS). | | | | | | 2.)TWO SETS OF PERMIT DOCUMENTS REQUIRED.ONLY ONE | | | INSTALLATION SCHEDULE WAS PROVIDED. | | | | | | 3.)PROVIDE A FLOOR PLAN SHOWING WORK LOCATION. | | | | | | 4.)PROVIDE A DETAIL FOR THE RAFTER REPAIR.INCLUDE | | | LOCATIONS ON THE FLOOR PLAN. | | | | | | 5.)PROVIDE A DETAIL FOR THE FLOOR JOIST REPAIR. | | | | | | 6.)SUBMIT A DOOR PRODUCT APPROVAL.TWO SETS | | | REQUIRED. | | | | | | 7.)PROVIDE A SCUPPER DETAIL, TOTAL SF AREA.DOES | | | THIS BUILDING HAVE A PARAPET?PROVIDE TOTAL SF ROOF | | | AREA.PLUMBING REVIEW MAY BE REQUIRED. |
|