| 2007-08-09 15:17:35 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 |
| | EXISTING BUILDING CODE |
| | FBC*CITY OF WEST PALM BEACH |
| | AMENDMENTS TO THE FBC2004 |
| | |
| | ROOFING PERMIT; ONLY CHECKED ITEMS APPLY |
| | |
| | ____1.)A NOTICE OF COMMENCEMENT MUST BE FILED WITH |
| | THE CLERK OF COURTS PRIOR TO PERMIT PICKUP, FS713.13. |
| | |
| | _XX_2.)PROVIDE INFORMATION IN REGARDS TO THE |
| | EXISTING ROOF.IF ANY OTHER MATERIAL IS INSTALLED |
| | OTHER THAN TILE, ENGINEERING WILL BE REQUIRED TO |
| | ADDRESS THE ADDITIONAL DEAD LOAD FBC R301, FBC16. |
| | |
| | ____3.)FLORIDA STATE OR LOCAL PRODUCT APPROVAL |
| | REQUIRED IN ADDITION TO THE EVALUATION REPORT |
| | SUBMITTED, FAC9B72.WWW.FLORIDABUILDING.ORG |
| | |
| | ____4.)FOR THE FLAT DECK, SELECT THE APPROVED |
| | ASSEMBLY YOU ARE USING.ALSO INDICATE WHICH FASTENER |
| | YOU ARE USING IF THE OPTIONS HAVE DIFFERENT PRESSURE |
| | LIMITATIONS. |
| | |
| | ____5.)FOR THE FLAT DECK, SPECIFY THE ENHANCED |
| | FASTENING FOR CORNER AND PERIMETER ZONES. |
| | |
| | _XX_ 6.)ON THE TILE PRODUCT APPROVAL, INDICATE WHICH |
| | METHOD OF ATTACHMENT YOU ARE USING.IF YOU SELECT FOAM |
| | ADHESIVE, PRODUCT APPROVALS REQUIRED FAC9B72. |
| | |
| | _XX_ 7.)CONTACT KEN CONRAD, CHIEF BUILDING INSPECTOR, |
| | 561-805-6666 IN REGARDS TO WEATHERBLOCKING REQUIRED FOR |
| | HANDMADE TILE.THIS MUST BE DONE PRIOR TO |
| | RESUBMITTAL. |