| Plan Review Notes For Permit 07080268 |
| Permit Number |
07080268 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-16 10:43:19 | ***DENIED*** | | | | | | 1) OK | | | | | | 2) OK | | | | | | 3) SHEET A2 HAS BEEN REFERENCED FOR CORRECTION BUT NO | | | NOTE WAS FOUND. PLEASE BE ADVISED THAT IN ADDITION TO | | | APPLICABLE BUILDING CODES, WORK, SPECIFICALLY LIFE | | | SAFETY SHALL COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 4) SHEET A2 WAS REFERENCED FOR CORRECTION BUT NO NOTE | | | WAS FOUND. PLEASE ADD TO PLANS. | | | | | | 5) INTERIOR FINISH CLASSIFICATION TO BE PROVIDED IN | | | TERMS OF CLASS A,B,ORC. INFORMATION SHALL BE SPECIFIC | | | TO THIS SCOPE OF WORK AND NOT GENERAL. | | | | | | 6) SMOKE ALARM LOCATIONS HAVE BEEN ADDED TO PLANS. | | | SHEET A4 DOES REFERENCE SMOKE DETECTORS UNDER | | | ELECTRICAL NOTES. PLEASE CORRELATE INFORMATION AS THE | | | TERM SMOKE DETECTOR WOULD INDICATE A FIRE ALARM | | | SYSTEM. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|