| 2007-09-07 09:12:26 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & |
| | REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST |
| | PALM BEACH AMENDMENTS TO CHAPTER 1 (WPB), FLORIDA |
| | ADMINISTRATIVE CODE (FAC), AND FLORIDA STATUTES (FS). |
| | |
| | *** DENIED *** |
| | 1) THE ENGINEER J. DAVID PUGA PRINTED NAME AND LICENSE |
| | NUMBER IN TITLE BLOCK IS NOT LEGIBLE, SEE FAC |
| | 61G15-23.002 (2). PLEASE CORRECT. |
| | |
| | 2) SHOW TYPE OF DRY CLEANING SYSTEM I, II, III, IV, OR |
| | V. SEE MECH. CH. 2. AND SHOW HOW THE PLANT WILL COMPLY |
| | WITH MECH. 502.6, 502.6.1, AND 502.6.2 REGARDING |
| | VENTILATION. |
| | |
| | 3) PLEASE SUBMIT DETAILED MANUFACTURER'S |
| | SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR THE |
| | GAS BOILER AND GAS CLOTHES DRYER. |
| | |
| | 4) STATE ON PLAN IF GAS CLOTHES DRYER IS TYPE 1 OR 2. |
| | IF TYPE 2 PROVIDE A DETAIL SHOWING INSTALLATION OF THE |
| | EXHAUST TO COMPLY WITH MECH. 504.7 REGARDING 6" |
| | CLEARANCE. |
| | |
| | 5) SHOW HOW THE GAS CLOTHES DRYER COMPLIES WITH MECH. |
| | 504.5 REGARDING MAKE-UP AIR. |
| | |
| | 6) STATE OR SHOW WERE THE CLOTHES DRYER EXHAUST WILL |
| | TERMINATE. IF AT THE SIDE WALL IT MAY NOT TERMINATE |
| | NEAR THE WATER CHILLER, SEE MECH. 501.2. |
| | |
| | 7) SHOW COMPLIANCE WITH MECH. 1004.3 GUARDING 18" |
| | CLEARANCE AROUND GAS BOILER. |
| | |
| | 8)PLEASE SUBMIT PRODUCT APPROVAL FOR THE 24X24 WALL |
| | LOUVERS, SEE FS 553.842(1) AND FAC RULE 9B-72, |
| | 9B-72.005, AND FAC 9B-72.010(31)(C). |
| | |
| | **PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION |
| | AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE |
| | FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE |
| | SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG. |
| | PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT |
| | IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT |
| | HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR |
| | LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE |
| | 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG. |
| | |