| 2007-09-05 13:43:21 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 FUEL GAS. |
| | ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| | REQUIREMENTS. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1. SHEET P-1 GAS RISER DIAGRAM: PLEASE CORRELATE THE |
| | TYPE OF GAS BEING USED. "GAS NOTES" ARE INDICATING A |
| | NATURAL GAS SIZING TABLE FOR 0.5 PSI AND THE "GAS |
| | TABLE" IS INDICATING LP SERVICE LOAD AND LP APPLIANCE. |
| | THIS IS CONFUSING, PLEASE CLEARLY INDICATE THE GAS TYPE |
| | ON THE RESUBMITTAL. PER FBC-2004 CHAPTER 1 SECTION |
| | 106.1.1, CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT |
| | CLARITY TO INDICATE THE LOCATION, NATURE, AND EXTENT OF |
| | THE WORK PROPOSED. |
| | |
| | 2. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | NOTE: THERE IS NO CLEAR INDICATION OF THE DELIVERY |
| | PRESSURE BEING INDICATED ON THE PRINTS OTHER THAN THE |
| | SIZING TABLE IN THE "GAS NOTES". PLEASE DO THIS ON THE |
| | RESUBMMITTAL. |
| | |
| | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO |
| | VERIFY COMPLIANCE WITH |
| | STANDARDS NFPA 54, NFPA 58, AND THE |
| | FBC-2004 FUEL GAS CODE SEC 402.2. |
| | NOTE: PLEASE SUBMIT MANUFACTURER SPECIFICATION SHEETS |
| | FOR THE DRYER AND THE BOILER WITH THE MANUFACTURER |
| | NAME, MODEL NUMBER, BTU LOAD, AND A LISTING FROM A |
| | NATIONALLY RECOGNIZED TESTING LABORATORY (NRTL) ON THE |
| | RESUBMITTAL. |
| | |
| | 4. CLEARLY SHOW THE LOCATION AND CAP- |
| | ACITY OF LP TANK(S), TYPE OF TANK (DOT |
| | OR ASME), THE DISTANCE OF THE TANK FROM |
| | THE BUILDING AND ADJACENT PROPERTY LINES |
| | THE DISTANCE OF THE TANK FROM ALL SOUR- |
| | CES OF IGNITION, OTHER CONTAINERS, BUILD |
| | INGS, AND THE LOCATION OF ANY BUILDING |
| | OPENINGS BELOW THE RELIEF VALVE OF THE |
| | TANK PER NFPA 58, TABLE 3-2.2.2. |
| | |
| | 5. CLEARLY INDICATE ON THE PLAN IF THE |
| | LP TANK IS ABOVE OR BELOW GROUND, AND |
| | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES |
| | PER NFPA 58. IF THE TANK |
| | IS BELOW GROUND THE CONTAINER SHALL BE |
| | SECURILY ANCHORED PER NFPA 58 SECTION |
| | 6.6.1. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| | PLEASE REPLACE ONLY SHEETS |
| | WHICH HAVE CHANGED, PLEASE INCLUDE A |
| | TRANSMITTAL LETTER INDICATING HOW EACH |
| | ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| | OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| | ONLY. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING IN RED INK |
| | ON THE INDICATED PLAN SHEETS BY THIS PLANS EXAMINER FOR |
| | REFERENCE FOR THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |