| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} 301.5 FBC EXISTING BUILDING CODE. THE DESIGN |
| | PROFESSIONAL OR OWNER MUST ELECT THE LEVEL OF |
| | ALTERATION PURSUANT TO SECTIONS 303, 304 AND 305 OF THE |
| | EXISTING BUILDING CODE. PLEASE DECLARE SAME ON THE |
| | PLAN. |
| | |
| | 2} INDICATE PER 230.2 WHY ANOTHER SERVICE AT THIS |
| | LOCATION IS WARRANTED. ALSO SEE 230.72. |
| | |
| | 3} INDICATE COMPLIANCE WITH THE APPLICABLE SECTIONS OF |
| | CHAPTER 13 ENERGY EFFICIENCY, FBC. |
| | |
| | 4} SEE 306.2 FOR OCCUPANCY CLASSIFICATION OF A DRY |
| | CLEANER, F-1. CHANGE ON SHEET A1. |
| | |
| | 5}INDICATE COMPLIANCE WITH NFPA-32, DECLARE PLANT |
| | TYPE SO THAT ELECTRICAL INSTALLATION CLASS AND DIVISION |
| | CAN BE DETERMINED. |
| | |
| | 6} PROVIDE AN EQUIPMENT SCHEDULE FOR EQUIPMENT BEING |
| | INSTALLED, WITH SPECIFICATIONS AND ELECTRICAL |
| | REQUIREMENTS. |
| | |
| | 7} COMPLY WITH NFPA-79 WHERE APPLICABLE. |
| | |
| | PLEASE REMOVE OLD SHEETS, INSERT NEW |
| | ONES, SUBMIT OLD SHEETS TO EXPEDITE |
| | REVIEW AND SUBMIT WRITTEN RESPONSE TO |
| | THE COMMENTS MADE IN THIS REVIEW. |
| | |
| | INDICATE THE CODE CYCLES THIS PROJECT WAS DESIGNED |
| | UNDER. 2004 FBC, 2005 NEC ETC. ADD TO NOTES FOR CLARITY |
| | IN THE FIELD. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |