| Plan Review Notes For Permit 07080262 |
| Permit Number |
07080262 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2007-11-21 14:00:34 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW. | | | | | | 1) NOTE: PLEASE COMPLETE CIRCUITING. PLANS NOW SHOW TWO | | | CIRCUITS GOING TO SHED/BUILDING. | | | FBC 106.1.2, | | | | | | 2) NOTE: PLEASE SHOW THE LOCATION OF THE DISCONNECT AS | | | REQUIRED PER 225.31-225.39 | | | | | | 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM | | | PER 250.50, 250.32 | | | | | | 4) NOTE: PLEASE LIST RELEVANT CODE. NFPA-70 2005 | | | | | | | | | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR | | | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF | | | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, | | | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO | | | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS | | | REVIEWER. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|