Plan Review Notes
Plan Review Notes For Permit 07080261
Permit Number 07080261
Review Stop E
Sequence Number 3
Notes
Date Text
2008-07-18 08:26:41** DENIED **
  
 1) NOTE: PERMIT APPLICATION IS MISSING FROM PACKAGE.
 NEEDS NEW OR PLEASE SUBMIT ORIGINAL.
  
 2) NOTE: PLEASE SHOW THE LOCATION OF THE REQUIRED
 DISCONNECT AT THE DETACHED BUILDING/STRUCTURE. THE
 PREVIOUS REVIEW REQUESTED TO *SHOW* THE LOCATION TO
 COMPLY WITH 225.31-225.39.
 110.26 ETC
  
 3) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO
 COMPLETION OF THE GROUNDING ELECTRODE SYSTEM PER
 250.50, 250.32, 250.66. THE PLANS ONLY NOTE GROUND
 RODS. NO CONDUCTOR ETC.?
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  
  