| 2008-07-18 08:26:41 | ** DENIED ** |
| | |
| | 1) NOTE: PERMIT APPLICATION IS MISSING FROM PACKAGE. |
| | NEEDS NEW OR PLEASE SUBMIT ORIGINAL. |
| | |
| | 2) NOTE: PLEASE SHOW THE LOCATION OF THE REQUIRED |
| | DISCONNECT AT THE DETACHED BUILDING/STRUCTURE. THE |
| | PREVIOUS REVIEW REQUESTED TO *SHOW* THE LOCATION TO |
| | COMPLY WITH 225.31-225.39. |
| | 110.26 ETC |
| | |
| | 3) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO |
| | COMPLETION OF THE GROUNDING ELECTRODE SYSTEM PER |
| | 250.50, 250.32, 250.66. THE PLANS ONLY NOTE GROUND |
| | RODS. NO CONDUCTOR ETC.? |
| | |
| | IF THERE ARE ANY QUESTIONS, PLEASE CALL. |
| | |
| | IMPORTANT** |
| | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP |
| | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE |
| | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED |
| | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. |
| | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID |
| | ANY DELAYS. |
| | |