2007-11-21 13:57:07** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW.
  
 1) NOTE: PLEASE COMPLETE CIRCUITING.
 FBC 106.1.2,
  
 2) NOTE: PLEASE SHOW THE LOCATION OF THE DISCONNECT AS
 REQUIRED PER 225.31-225.39
  
 3) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEM
 PER 250.50, 250.32
  
 4) NOTE: PLEASE LIST RELEVANT CODE. NFPA-70 2005
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  