Plan Review Notes For Permit 07080261
Permit Number 07080261
Review Stop P
Sequence Number 1
Notes
Date Text
2007-09-21 17:01:22DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. SHTS 1 & 2 THE DATE THE SIGNATURE AND SEAL ARE
 AFFIXED TO THE PLANS IS REQUIRED.--THE PRINTED NAME
 OF THE PERSON SEALING THE DOCUMENT IS REQUIRED ON EACH
 SHEET.--THE SIGNATURE IS REQUIRED. IT APPEARS THAT
 INITIALS ARE USED. IF INDEED THIS IS THE LEGAL
 SIGNATURE OF THE ARCHITECT, THEN A SIGNED, SEALED,
 NOTORIZED LETTER SHALL BE SUBMITTED INDICATING THE
 LEGAL SIGNATURE FOR OUR FILES. FAC 61G1-16.003,
 61G1-16.004(5)(6) & FS 481.2055.
  
 2. PLANS INDICATE THE OCCUPANCY OF THE BUILDING AS
 STORAGE. PER TABLES 1004.1.2 AND 104.3.1 TOILET ROOMS,
 A SERVICE SINK, A DRINKING FOUNTAIN AND POSSIBLY AN EYE
 WASH AND/OR EMERGENCY SHOWER MAY BE REQUIRED. ALSO SEE
 SECTIONS 403.2, 403.4 & 411.
  
 3. PLEASE INDICATE WHAT WILL BE STORED IN THE STORAGE
 BUILDING. MSDS SHEETS MAY BE REQUIRED ACCORDING TO THE
 TYPE OF MATERIAL BEING STORED. SECTION 106.1.1.
  
 4. HOT WATER WILL BE REQUIRED TO THE SERVICE SINK PER
 SECTION 607.1. PLEASE INDICATE THE LOCATION OF THE
 WATER HEATER.
  
 5. SUBMIT A SANITARY ISOMETRIC RISER DIAGRAM SHOWING
 ALL PIPE SIZES, TRAPS & VENTS AS WELL AS A WATER
 ISOMETRIC RISER DIAGRAM SHOWING ALL PIPE SIZES, VALVES
 AND AN RPZV BACKFLOW ON THE WATER SERVICE TO THE
 BUILDING. SECTION 106.3.5.1.3(3)(5)(6)(8)(10)(13).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID
 SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY
 ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU
 FOR YOUR ANTICIPATED COOPERATION.
  