Plan Review Notes For Permit 07080261
Permit Number 07080261
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2007-10-03 18:03:18*****DENIED******
  
  
 1.THE ADDRESS OF THE PROJECT SITE SHALL BE IN THE
 TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 3.THE SCOPE OF WORK SHALL NOT INTERFERE OR HINDER
 EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING ROADS, FIRE LANES).
  
 4.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 5.DECLARE THE CONTENTS OF THIS STORAGE OCCUPANCY BY
 CLASSIFYING AS LOW HAZARD, ORDINARY HAZARD, OR HIGH
 HAZARD.
  
 6.SPECIFY THE INTERIOR WALL AND CEILING FINISH
 MATERIALS IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.SHOW THE LOCATION OF THE 2A:10BC RATED FIRE
 EXTINGUISHER.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE ON THE PLAN EACH COMMENT WAS
 ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722