Plan Review Notes
Plan Review Notes For Permit 07080261
Permit Number 07080261
Review Stop B
Sequence Number 1
Notes
Date Text
2007-09-16 20:17:51BEAR LAKES COUNTRY CLUB 1901 VILLAGE BLVDBUILDING
 PLAN REVIEW
 PERMIT: 07080261
 ADD: 1901 VILLAGE BLVD
 CONT: GSP & ASSOC
 TEL: (561)697-8444
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 2)PROVIDE FLOOD ZONE ELEVATION CERTIFICATE FOR NEW
 CONSTRUTION WITH BASE FLOOD ELEVATION, CITY CODE
 REQUIRES AN ADDITIONAL 6". THIS IS A LOMR REQUIRING A
 FINISH FLOOR HEIGTH OF 16'-6".
  
 3) THERE IS ONLY ONE SET OF PLANS, (2) SETS OF ALL
 PLANS, PRODUCT APPROVAL, SUBMITTALS AND OR REPORTS WILL
 BE REQUIRED FOR PERMIT ISSUANCE. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 4)110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .
 5)PLANS INDICATE PLYWOOD SUBSHEATHING TO BE WITHIN 6"
 OF GRADE, ALSO 2X4 STUDS.
 2304.11.2.2 FRAMING.
 WOOD FRAMING MEMBERS, INCLUDING WOOD SHEATHING, WHICH
 REST ON EXTERIOR FOUNDATION WALLS AND ARE LESS THAN 8
 INCHES (203 MM) FROM EXPOSED EARTH SHALL BE OF
 NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD. WOOD
 FRAMING MEMBERS AND FURRING STRIPS ATTACHED DIRECTLY TO
 MASONRY OR CONCRETE WALLS SHALL BE OF APPROVED
 NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD.
  
 2304.11.2.3 SLEEPERS AND SILLS.
 SLEEPERS AND SILLS ON A CONCRETE OR MASONRY SLAB THAT
 IS IN DIRECT CONTACT WITH EARTH SHALL BE OF NATURALLY
 DURABLE OR PRESERVATIVE-TREATED WOOD.
  
 2304.11.2.5 WOOD SIDING.
 CLEARANCE BETWEEN WOOD SIDING AND EARTH ON THE EXTERIOR
 OF A BUILDING SHALL NOT BE LESS THAN 6 INCHES (152 MM)
 EXCEPT WHERE SIDING, SHEATHING AND WALL FRAMING ARE OF
 NATURALLY DURABLE OR PRESERVATIVE-TREATED WOOD.
  
 6) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES(3 IF THRESHOLD OR RESIDENT INSPECTOR)
 OF PRODUCT TESTING REPORTS ,MISSING REPORTS ARE AS
 FOLLOWS:
 A) WINDOWS
 B) DOORS
 C) TRUSS ANCHORS & STRAPS
 D) HARDIE PLANK
 E) ROOFING ASSEMBLIES:
 UNDERLAYMENT
 ROOF TILE
  
 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72.
  
 8) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 9) THIS STRUCTURE USED TO BE A TRASH ENCLOSURE WITH A
 CONCRETE SLAB,HOW ARE YOU GOING TO TERMITE TREAT THE
 SLAB AND PROVIDE A VAPOR BARRIER?
  
 10)PLANSFAIL TO INDICATE ATTIC VENTILATION: 1203.2
 ATTIC SPACES. ENCLOSED ATTICS AND ENCLOSED RAFTER
 SPACES FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO
 THE UNDERSIDE OF ROOF FRAMING MEMBERS SHALL HAVE CROSS
 VENTILATION FOR EACH SEPARATE SPACE BY VENTILATING
 OPENINGS PROTECTED AGAINST THE ENTRANCE OF RAIN.
 BLOCKING AND BRIDGING SHALL BE ARRANGED SO AS NOT TO
 INTERFERE WITH THE MOVEMENT OF AIR. A MINIMUM OF 1 INCH
 (25 MM) OF AIRSPACE SHALL BE PROVIDED BETWEEN THE
 INSULATION AND THE ROOF SHEATHING. THE NET FREE
 VENTILATING AREA SHALL NOT BE LESS THAN 1 / 150 OF THE
 AREA OF THE SPACE VENTILATED, WITH 50 PERCENT OF THE
 REQUIRED VENTILATING AREA PROVIDED BY VENTILATORS
 LOCATED IN THE UPPER PORTION OF THE SPACE TO BE
 VENTILATED AT LEAST 3 FEET (914 MM) ABOVE EAVE OR
 CORNICE VENTS WITH THE BALANCE OF THE REQUIRED
 VENTILATION PROVIDED BY EAVE OR CORNICE VENTS.
  
 11) 1209.2 ATTIC SPACES. AN OPENING NOT LESS THAN 20
 INCHES BY 30 INCHES (559 MM BY 762 MM) SHALL BE
 PROVIDED TO ANY ATTIC AREA HAVING A CLEAR HEIGHT OF
 OVER 30 INCHES (762 MM). A 30-INCH (762 MM) MINIMUM
 CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT
 OR ABOVE THE ACCESS OPENING.
  
 12)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
  
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
  
  
  