Text |
| 2007-08-16 14:03:59 | DENIED |
| | REFERENCE: |
| | ** FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING POOLS. |
| | ** FBC-2004 PLUMBING. |
| | ** FBC-2004 CHAPTER 1, THE CITY OF |
| | WEST PALM BEACH AMENDMENTS. |
| | ** FLORIDA ADMINISTRATIVE CODE. |
| | ** FLORIDA STATUTES. |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE: |
| | |
| | 1) COMPLY WITH FBC-2004 SEC 424.2, OR |
| | FBCR-2004 SEC R4101 PRIVATE SWIMMING |
| | POOLS. (ADD TO NOTES) |
| | |
| | 2) FBC-2004 SEC 424.2.6.1, OR FBCR-2004 |
| | SEC R4101.6.1 ENGINEERING DESIGN, |
| | CONSTRUCTION AND WORKMANSHIP. |
| | ANSI/NSPI-5. (ADD TO NOTES) |
| | |
| | 3) FBC-2004 424.2.6.6.2, OR FBCR-2004 |
| | SEC R4101.6.6.2 SHOW COMPLIANCE WITH |
| | ANSI/ASME A112.19.8M. PROVIDE MODEL |
| | NUMBER AND MANUFACTURER INFORMATION FOR SUCTION |
| | FITTINGS (MAIN DRAINS). |
| | (SUBMITTAL OR ADD TO NOTES) |
| | |
| | 4) FBC-2004424.2.6.6.3, OR FBCR-2004 SEC R4101.6.6.3 |
| | (1,2,3) ENTRAPMENT AVOIDANCE. |
| | NOTE: POOL DETAIL OF THE VENT PIPE SIZE IS TO VAGUE |
| | PLEASE CLARIFY THE EXACT SIZE OF THE VENT ON THE |
| | RESUBMITTAL AND PLEASE ADD TO THE VENT DETAIL THE |
| | FOLLOWING "LABEL VENT: POOL SAFETY DEVICE - DO NOT |
| | HANDLE" |
| | |
| | 5) FBC-2004 SEC. 424.2.6.6.5, OR |
| | FBCR-2004 SEC. R4101.6.6.5 WHERE |
| | PROVIDED, THE VACUUM OR PRESSURE CLEANER |
| | FITTING SHALL BE LOCATED AT LEAST 6" AND |
| | NOT GREATER THAN 12" BELOW THE MINIMUM |
| | OPERATING WATER LEVEL OR AS AN |
| | ATTACHMENT TO THE SKIMMER. |
| | (DETAIL REQUIRED WITH THE MAKE AND MODEL NUMBER OF THE |
| | CLEANER FITTING) |
| | |
| | 6) FBC-2004 SEC. 424.2.7.2, OR |
| | FBCR-2004 SEC. R4101.7.2 PUMPS AND |
| | EQUIPMENT SHALL BE MOUNTED ON A |
| | SUBSTANTIAL BASE IN A MANNER THAT WILL |
| | ELIMINATE STRAIN ON PIPING.SLAB SHALL |
| | BE A NOMINAL 4" THICK. (DETAIL REQUIRED) |
| | |
| | 7) FBC-2004 SEC. 424.2.9, OR FBCR-2004 SEC. |
| | R4101.9 WATER SUPPLY, LOCAL ORD. |
| | #2853-95, BACKFLOW REQUIRED ON WATER |
| | SERVICE.(ADD TO NOTES) |
| | |
| | 8) FBC-2004 SEC. 424.2.12.1, OR |
| | FBCR-2004 SEC. R4101.12.1 PRESSURE |
| | TESTS. PER MANUFACTURE RECOMMENDATIONS, |
| | NO AIR TEST SHALL BE APPROVED FOR PVC |
| | PIPE AND FITTINGS. (ADD TO NOTES) |
| | |
| | 9) FBC-2004 SEC. 424.2.13.2, OR |
| | FBCR-2004 SEC.R4101.13.2 JOINTS AND |
| | CONNECTIONS, FBC PLMG SEC 605.21, PURPLE |
| | PRIMER REQUIRED ON PVC PIPING.(ADD TO |
| | NOTES) |
| | |
| | 10) FBC-2004 SEC. 424.2.20 OR FBCR-2004 SEC. R4101.20 |
| | FILTERS. THE ENTIRE DESIGN OF MATCHED COMPONENTS SHALL |
| | HAVE SUFFICIENT CAPACITY TO PROVIDE A COMPLETE TURNOVER |
| | OF POOL WATER IN 12 HOURS OR LESS. |
| | NOTE: PLEASE PROVIDE THE TURNOVER TIME OF THE POOL ON |
| | THE RESUBMITTAL. |
| | |
| | 11) THE ENGINEERING FIRM LISTED ON THE TITLE BLOCK |
| | SHALL INDICATE THE CERTIFICATE OF AUTHORIZATION NUMBER |
| | ALONG WITH OTHER INFORMATION REQUIRED BY 61G15-23.002 |
| | FLORIDA ADMINISTRATIVE CODE. |
| | |
| | END OF COMMENTS: |
| | |