| 2007-10-22 15:08:52 | RESIDENTIAL ADDITION BUILDING REVIEW SECOND CHECKLIST. |
| | REVIEW DONE UNDER EXISTING BUILDING CODE 2004,FLORIDA |
| | RESIDENTIAL CODE 2004 AND FBC 2004 WITH 2007 |
| | REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED |
| | BY SEC. 713.13 FLORIDA STATUTE. (REPEAT COMMENT). |
| | |
| | 2- TRUSS ANCHOR SCHEDULE: |
| | A) REVISE NUMBER OF NAILS SPECIFIED FOR CONNECTOR E. |
| | SEE SIMPSON CATALOG AND REVISE AS REQUIRED. (REPEAT |
| | COMMENT). OTHERWISE PROVIDE COMPLETE ENGINEERING |
| | ANALYSIS FOR NUMBER OF NAILS THAT DIFFER FROM THOSE |
| | TESTED AND PUBLISHED BY THE MANUFACTURER. SEC. 106.1.2 |
| | CITY AMENDMENTS TO FBC 2004 IN REGARD TO SEC. 1609 FBC |
| | 2004. |
| | |
| | B) SIMPSON CONNECTORS B AND C DON'T RESIST THE |
| | UPLIFT LOADS CALCULATED ON THE ROOF FRAMING PLAN ON |
| | SHEET 6. REVISE AS REQUIRED. |
| | |
| | 3- SHEET 9: |
| | A) REVISE TYPE OF NAIL SPECIFIED ON ROOF SHEATHING |
| | NAILING SCHEDULE.SEC. R803.2.3.1 OF 2004 FLORIDA |
| | RESIDENTIAL CODE REQUIRES 8D RING SHANK NAILS, NOT 8D |
| | NAILS. (REPEAT COMMENT). |
| | |
| | B) REVISE PLYWOOD NAILING DIAGRAM TO MATCH |
| | INFORMATION REQUESTED ON ITEM 3(A) ABOVE. |
| | |
| | 4- REVISE SIZE OF HOLES AND ANCHORS SPECIFIED FOR |
| | COLUMN BASE STEEL PLATE ON DETAIL 1 ON SHEET 4AND |
| | DETAIL 3 ON SHEET 7 TO MATCH.ONE DETAIL CALLS FOR |
| | 1/2" BOLTS AND THE OTHER CALLS FOR 5/8" BOLTS. REVISE |
| | AS REQUIRED. |
| | |
| | 5- SPECIFY BUILDING CONSTRUCTION TYPE AS REQUIRED BY |
| | SEC. 602.1 FBC 2004. (REPEAT COMMENT). |
| | |
| | 6- REVISE FINISH CEILING SPECIFICATIONS FOR PATIO. |
| | ROOF FRAMING NEEDS TO BE ADJUSTED WHEN USING "GREEN |
| | BOARD". SEE ATTACHED COPY OF TECHNICAL INFORMATION FROM |
| | THE GYPSUM COMPANY. SEC. 106.1.2 CITY AMENDMENTS TO FBC |
| | 2004. |
| | |
| | 7- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | 13-600.1.C.2 FBC 2004. |
| | ***NOTE: SCOPE OF WORK INCLUDES NEW PATIO AND NEW ROOF |
| | OVER ENTIRE HOUSE THAT'S WHY ENERGY CALCULATIONS ARE |
| | REQUIRED. |
| | |
| | 8- ATTIC ACCESS IS SHOWN ON ROOF FRAMING PLAN, BUT |
| | SIZE IS NOT SPECIFIED.SPECIFY SIZE AS REQUIRED BY |
| | SEC. R807 OF 2004 FLORIDA RESIDENTIAL CODE. |
| | |