| 2007-12-03 10:13:17 | |
| | |
| | |
| | |
| | ** DENIED 3RD REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE |
| | STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW |
| | COMMENTS BASED ON REVISED AND NEW PLANS SUBMITTED. |
| | |
| | 1) NOTE: PLEASE SEE PLANS MAY NOT CONTAIN ANY WHITE-OUT |
| | AND NO HAND DRAWN CHANGES ARE PERMITTED. |
| | PLEAS HAVE SHEETS REPRINTED AND THEN RE-SIGNED, DATED |
| | AND SEALED BY THE DESIGN PROFESSIONAL. |
| | PLEASE SEE THE NEW PHOTO-METRIC SHEETS SUBMITTED DO NOT |
| | CONTAIN ANY TITLE BLOCKS AS REQUIRED PER FAC |
| | 61G15-23.002. PLEASE COMPLETE. PLEASE SEE THE FOLLOWING |
| | COMMENT FOR REVISED SHEETS AS NEEDED. |
| | |
| | 2) NOTE: PLEASE SEE THE LIGHTING LEVELS DO NOT MEET THE |
| | MINIMUM PER NFPA-101 LIFE SAFETY CODE. |
| | PLEASE SEE 7.8.1.3 AS THE NORMAL LIGHTING LEVELS ON |
| | STAIRS MUST BE 10FT CANDLES MINIMUM AND IS PERMITTED TO |
| | GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS. |
| | PLEASE SEE THE LEVELS ARE ONLY SUBMITTED AND SHOWN FOR |
| | THREE STAIRS WHEN PLANS ACTUALLY CONTAIN MORE STAIRS |
| | WHICH ARE BEING WORKED ON IN THIS SCOPE AND ARE PART OF |
| | THE EGRESS, EXIT DISCHARGE AREA. PLEASE COMPLETE ALL |
| | AREAS AS NOTED ON PREVIOUS REVIEWS. |
| | ** PLEASE BE SURE TO INDICATE THE LEVELS UNDER |
| | EMERGENCY ALSO BASED ON FIXTURES PROVIDED. |
| | |
| | 3) NOTE: PLEASE SEE THAT THE EQUAL-POTENTIAL BONDING |
| | DETAILS ADDED ARE TO MEET NOTE #1. |
| | |
| | *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |