Plan Review Notes
Plan Review Notes For Permit 07080220
Permit Number 07080220
Review Stop E
Sequence Number 3
Notes
Date Text
2007-12-03 10:13:17 
  
  
  
 ** DENIED 3RD REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING ALONG WITH SOME NEW
 COMMENTS BASED ON REVISED AND NEW PLANS SUBMITTED.
  
 1) NOTE: PLEASE SEE PLANS MAY NOT CONTAIN ANY WHITE-OUT
 AND NO HAND DRAWN CHANGES ARE PERMITTED.
 PLEAS HAVE SHEETS REPRINTED AND THEN RE-SIGNED, DATED
 AND SEALED BY THE DESIGN PROFESSIONAL.
 PLEASE SEE THE NEW PHOTO-METRIC SHEETS SUBMITTED DO NOT
 CONTAIN ANY TITLE BLOCKS AS REQUIRED PER FAC
 61G15-23.002. PLEASE COMPLETE. PLEASE SEE THE FOLLOWING
 COMMENT FOR REVISED SHEETS AS NEEDED.
  
 2) NOTE: PLEASE SEE THE LIGHTING LEVELS DO NOT MEET THE
 MINIMUM PER NFPA-101 LIFE SAFETY CODE.
 PLEASE SEE 7.8.1.3 AS THE NORMAL LIGHTING LEVELS ON
 STAIRS MUST BE 10FT CANDLES MINIMUM AND IS PERMITTED TO
 GO DOWN TO 1FT CANDLE UNDER EMERGENCY CONDITIONS.
 PLEASE SEE THE LEVELS ARE ONLY SUBMITTED AND SHOWN FOR
 THREE STAIRS WHEN PLANS ACTUALLY CONTAIN MORE STAIRS
 WHICH ARE BEING WORKED ON IN THIS SCOPE AND ARE PART OF
 THE EGRESS, EXIT DISCHARGE AREA. PLEASE COMPLETE ALL
 AREAS AS NOTED ON PREVIOUS REVIEWS.
 ** PLEASE BE SURE TO INDICATE THE LEVELS UNDER
 EMERGENCY ALSO BASED ON FIXTURES PROVIDED.
  
 3) NOTE: PLEASE SEE THAT THE EQUAL-POTENTIAL BONDING
 DETAILS ADDED ARE TO MEET NOTE #1.
  
 *** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]