| 2007-11-04 10:26:05 | PLANS REMOVED FROM INCOMING AND WILL BE RETURNED TO |
| | INCOMING ONCE REVIEW IS COMPLETED WAITING FOR COMM |
| | BOARD. |
| | |
| | |
| | |
| | ** DENIED 2ND REVIEW ** |
| | |
| | ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL |
| | IN NEED OF ADDRESSING. |
| | AS SOME INFORMATION WAS STILL NOT SUBMITTED, A COMPLETE |
| | REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE. |
| | |
| | 1) NOTE: PLEASE SEE NOTES 3, 4 AND 5 FROM PREVIOUS |
| | REVIEW BELOW. |
| | |
| | NOTE#3, AS NO SCALE IS ON ELECTRICAL PLANS OR |
| | DIMENSIONS FOR LIGHTING ETC IS ALSO NOT ON PLANS, |
| | COMPLIANCE WITH THE CODES GIVEN CAN NOT BE DETERMINED. |
| | |
| | NOTE #4, A BONDING GRID IS NOTED, HOWEVER NO ENOUGH |
| | INFORMATION OR DETAILS IS PROVIDED FOR DIMENSIONS ETC. |
| | QUOTING ONE REQUIRED IN LIEU OF DETAIL IS NOT PERMITTED |
| | BY CODE. |
| | |
| | NOTE #5, NO PHOTO-METRICS SUBMITTED, NO REVIEW DONE. |
| | PLEASE AS THIS *IS* AS LIFE SAFETY ISSUE THE MINIMUM |
| | LIGHTING LEVELS FOR EXIT AND EGRESS PATHS AND DISCHARGE |
| | AREAS IS REQUIRED. |
| | |
| | 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| | REPEAT COMMENTS FOR CODE COMPLIANCE. |
| | THIS IS ONLY A NOTICE GIVEN AT THIS TIME. |
| | |
| | ******** NOTES FROM PREVIOUS REVIEWS ********* |
| | |
| | 3) NOTE: PLEASE INCLUDE THE INFORMATION FOR ALL NEW |
| | LIGHTING BEING PROPOSED ON PLANS. |
| | PLEASE INCLUDE VOLTAGE AND PROTECTION FOR FIXTURES PER |
| | 680.22. PLEASE INDICATE THE REQUIRED GFI RECEPTACLE |
| | WITHIN 20FT OF POOL. (NEW OR EXISTING). |
| | PLEASE SEE 411.4B IF ANY LIGHTING FIXTURES ARE LOW |
| | VOLTAGE (30VOLTS OR LESS). |
| | PLEASE INCLUDE CIRCUITING INFORMATION ON HOW AND WHERE |
| | THE POWER IS COMING FROM. (CONDUCTOR(S), GROUNDING, |
| | OVER CURRENT PROTECTION ETC. |
| | 408.4, 310.16, 240.4 |
| | |
| | 4) NOTE: PLEASE SEE 2005NEC680.26 FOR THE REQUIRED |
| | EQUAL-POTENTIAL BONDING GRID REQUIRED. |
| | |
| | 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ALL EGRESS |
| | STAIR LOCATIONS AND EGRESS PATHS UNDER NORMAL AND UNDER |
| | EMERGENCY CONDITIONS. |
| | PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2. |
| | PLEASE ALSO SEE FAC 61G15-33.004. |
| | |
| | |
| | ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| | COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| | THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| | NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| | NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| | REVIEWER. |
| | |
| | ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |