2007-11-04 10:26:05PLANS REMOVED FROM INCOMING AND WILL BE RETURNED TO
 INCOMING ONCE REVIEW IS COMPLETED WAITING FOR COMM
 BOARD.
  
  
  
 ** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME ITEMS FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 AS SOME INFORMATION WAS STILL NOT SUBMITTED, A COMPLETE
 REVIEW FOR CODE COMPLIANCE COULD NOT BE DONE.
  
 1) NOTE: PLEASE SEE NOTES 3, 4 AND 5 FROM PREVIOUS
 REVIEW BELOW.
  
 NOTE#3, AS NO SCALE IS ON ELECTRICAL PLANS OR
 DIMENSIONS FOR LIGHTING ETC IS ALSO NOT ON PLANS,
 COMPLIANCE WITH THE CODES GIVEN CAN NOT BE DETERMINED.
  
 NOTE #4, A BONDING GRID IS NOTED, HOWEVER NO ENOUGH
 INFORMATION OR DETAILS IS PROVIDED FOR DIMENSIONS ETC.
 QUOTING ONE REQUIRED IN LIEU OF DETAIL IS NOT PERMITTED
 BY CODE.
  
 NOTE #5, NO PHOTO-METRICS SUBMITTED, NO REVIEW DONE.
 PLEASE AS THIS *IS* AS LIFE SAFETY ISSUE THE MINIMUM
 LIGHTING LEVELS FOR EXIT AND EGRESS PATHS AND DISCHARGE
 AREAS IS REQUIRED.
  
 2) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE.
 THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
 ******** NOTES FROM PREVIOUS REVIEWS *********
  
 3) NOTE: PLEASE INCLUDE THE INFORMATION FOR ALL NEW
 LIGHTING BEING PROPOSED ON PLANS.
 PLEASE INCLUDE VOLTAGE AND PROTECTION FOR FIXTURES PER
 680.22. PLEASE INDICATE THE REQUIRED GFI RECEPTACLE
 WITHIN 20FT OF POOL. (NEW OR EXISTING).
 PLEASE SEE 411.4B IF ANY LIGHTING FIXTURES ARE LOW
 VOLTAGE (30VOLTS OR LESS).
 PLEASE INCLUDE CIRCUITING INFORMATION ON HOW AND WHERE
 THE POWER IS COMING FROM. (CONDUCTOR(S), GROUNDING,
 OVER CURRENT PROTECTION ETC.
 408.4, 310.16, 240.4
  
 4) NOTE: PLEASE SEE 2005NEC680.26 FOR THE REQUIRED
 EQUAL-POTENTIAL BONDING GRID REQUIRED.
  
 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ALL EGRESS
 STAIR LOCATIONS AND EGRESS PATHS UNDER NORMAL AND UNDER
 EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE FAC 61G15-33.004.
  
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]