| 2007-09-21 18:13:48 | DENIED |
| | REFERENCE: FBC-2004 PLUMBING |
| | FBC-2004 CHAPTER 1 |
| | FLORIDA ADMINISTRATIVE CODE |
| | FLORIDA STATUTES |
| | |
| | 1. ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME AND |
| | LICENSE NUMBER ON EACH SHEET AND IF PRACTICING THROUGH |
| | A DULY AUTHORIZED ENGINEERING BUSINESS, ENGINEERS SHALL |
| | LEGIBLY INDICATE THEIR NAME AND LICENSE NUMBER, AS WELL |
| | AS, THE NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION |
| | NUMBER OF THE ENGINEERING BUSINESS ON EACH SHEET. |
| | FAC61G15-23.002(2) & FS 471.025. |
| | |
| | 2. PLANS INDICATE THE DEMOLITION OF PLANTERS. PLEASE |
| | INDICATE IF THE PLANTER DRAINS WILL BE CONVERTED TO |
| | DECK DRAINS. SECTION 106.1.2.--IF THE DECK DRAINS |
| | WILL BE REMOVED, THEN DEAD ENDS SHALL BE PROHIBITED PER |
| | SECTION 704.5. |
| | |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY |
| | PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, |
| | WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION |
| | PAGE WHERE THE CHANGES CAN BE FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE ALL VOID |
| | SHEETS FROM ALL PLANS AND PLACE ONE SET OF THEM LOOSELY |
| | ON TOP OF THE COLLATED PLANS TO BE REVIEWED. THANK YOU |
| | FOR YOUR ANTICIPATED COOPERATION. |
| | |