Plan Review Notes
Plan Review Notes For Permit 07080220
Permit Number 07080220
Review Stop E
Sequence Number 1
Notes
Date Text
2007-09-08 18:33:16** DENIED **
  
  
  
 1) NOTE:PLEASE KNOW THAT ANY PERMIT APPLICATIONS
 WHICH ARE SUBMITTED AFTER DECEMBER 8TH, 2006 PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGES IN THE FBC WHICH MAY
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE LIST THE FOLLOWING ON ELECTRICAL SHEETS FOR THIS
 REVIEWER AT A MINIMUM.
 2004 FBC W/ 2006 REVISIONS
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE MISSING INFORMATION REQUIRED ON
 TITLE BLOCKS FOR THE ENGINEERING FIRM, ETC PER FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 AND FLORIDA STATUTES
 471.023.
 PLEASE SEE MISSING PRINTED NAME.
 PLEASE SEE MISSING PRINTED LICENSE NUMBER FOR PE.
 PLEASE SEE MISSING CERTIFICATE OF AUTHORIZATION NUMBER
 ALSO KNOWN AS THE ENGINEERING BUSINESS NUMBER.
 ** THIS IS REQUIRED FOR ALL SHEETS AND FOR ALL TRADES
 WHETHER OR NOT COMMENT IS MADE BY OTHER REVIEWER(S).
  
 3) NOTE: PLEASE INCLUDE THE INFORMATION FOR ALL NEW
 LIGHTING BEING PROPOSED ON PLANS.
 PLEASE INCLUDE VOLTAGE AND PROTECTION FOR FIXTURES PER
 680.22. PLEASE INDICATE THE REQUIRED GFI RECEPTACLE
 WITHIN 20FT OF POOL. (NEW OR EXISTING).
 PLEASE SEE 411.4B IF ANY LIGHTING FIXTURES ARE LOW
 VOLTAGE (30VOLTS OR LESS).
 PLEASE INCLUDE CIRCUITING INFORMATION ON HOW AND WHERE
 THE POWER IS COMING FROM. (CONDUCTOR(S), GROUNDING,
 OVER CURRENT PROTECTION ETC.
 408.4, 310.16, 240.4
  
 4) NOTE: PLEASE SEE 2005NEC680.26 FOR THE REQUIRED
 EQUAL-POTENTIAL BONDING GRID REQUIRED.
  
 5) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR ALL EGRESS
 STAIR LOCATIONS AND EGRESS PATHS UNDER NORMAL AND UNDER
 EMERGENCY CONDITIONS.
 PLEASE SEE NFPA-101 7.8.1.3, 7.9.2.2.
 PLEASE ALSO SEE FAC 61G15-33.004.
  
 ** PLEASE KNOW AS THERE IS INFORMATION NOT YET
 SUBMITTED FOR REVIEW, A FULL REVIEW FOR CODE COMPLIANCE
 CAN NOT BE DONE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]