Plan Review Notes
Plan Review Notes For Permit 07080208
Permit Number 07080208
Review Stop B
Sequence Number 1
Notes
Date Text
2007-08-31 07:47:04****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.)TWO SETS OF DOCUEMENTS REQUIRED FOR PERMITTING.
 DUE TO WORK LOAD, I AM UNABLE TO MAKE COPIES FOR
 CONTRACTORS.THERE IS A PHOTOCOPY MACHINE IN THE LOBBY
 PROVIDED.ONLY ONE INSTALLATION SCHEDULE WAS
 PROVIDED.
  
 2.)SEE SHEET 7 OF THE PRODUCT APPROVAL.A 3" EDGE
 DISTANCE REUIQRES A FACTOR OF .86.YOU HAVE
 HIGHLIGHTED THIS BUT HAVE NOT APPLIED THIS FACTOR TO
 YOUR ANCHOR SPACING.
  
 3.)INCLUDE THE SIDE ANCHOR SPACING ON THE
 INSTALLATION SCHEDULE.YOU MAY MODIFY OUR SUGGESTED
 FORM ANCHOR SPACING COLUMN FROM TOP/BOTTOM TO TOP/SIDE.
  
  